Chapt.1 System Configuration

Operation:

When the instruction input is ON, one set of message which is stored in the

source table (from start character to the trailing code) is transmitted through

the link port. The execution status is stored in the status flag.
The instruction input must be kept ON until the transmitting operation is
complete.

Example:

Source designation

Transfer size

Destination designation

D0010

HOO

H04

D0012

00012

D0015

HOO

H30

D0011

00500

D0013

Execution status

D0016

00000

D0500 (CPU register)

Link port

When R0001 is ON, one set of message (ended by the trailing code) stored in
the range of D0500 to D0511 (12 words) is transmitted through the link port.

Execution status:

HOOOO ... Normal complete

H0001 ... During transmitting the message
H0002 ... Communication busy (other receiving/transmitting

routine is executing)

H0003 ... During the reset operation
H0004 ... Send time-out (from start character to the trailing code)
H0005 ... Send message length error (no trailing code in the source

table)

Baudrate

Time-out setting

300, 600, 1200 bps

30 seconds

2400 bps

15 seconds

4800 bps

7 seconds

9600 bps

3 seconds

19200 bps

1.5 seconds

Remarks:

The instruction error flag (S0051) comes ON in the following cases, (no
operation)

• The leading address for the link port designation is other than 0.

• Transfer size is out of the range of 1 to 256.

• Mode setting of the link port is not the free ASCII mode.

• This instruction is programmed in the sub-program #1.

44

Sequence Controller S2T