beautypg.com

7 precautions for analog output modules, Cx)c ) – Toshiba SX 2000 User Manual

Page 140

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

(1)

Use a shielded twisted-pair cable for the analog output signal line, and wire

over the minimum distance. Wire the grounding of the cable shield on the

load side, (j) in the drawing below is the basic.

Sometimes, operation is more stable if the wiring is as in © or

(D.

3.7 Precautions for Analog Output Modules

3.7 Precautions for Analog Output Modules

©

Analog
Output

P<

module

N<

Analog
Output

P'

module

N<

Analog
Output

P<

module

N<

/1

\L

-a

A=

)

0

C

}

0

C

30

C

X)C

)

0

C

A

KT

T\

r ~pL

__T

l_

I'

A

(2)

Sometimes the conversion values are unstable, depending on the voltage

state of the external 24Vdc power supply.

If the conversion result is not stable, use a dedicated power supply for

analog.

(3)

All intrinsically shielded cables are fitted with ferrite choke adjacent to

analog inputs/outputs, and must have ground connections to grounded

metalwork within 5cm for applying to the EMC Directive.

6F8C0926

1 23