beautypg.com

Toshiba SX 2000 User Manual

Page 105

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Chapt.2 Specifications

A/D Conversion

Digital Value

Digital Value

(a) 4-20mA range :D=15.625xA-62.5

(b) 1-5V range :D=62.5xA-62.5

(c) 0-10V range :D=25xA

D: Digital value

A: Analog value

Data Format

XW

F

E

D

C

B

A

9

8

7

6

5

4

3

2

1

0

B

*

*

*

*

*

*

*

D

D

D

D

D

D

D

D

D: Data bit (8bits)

0-250 (HOO - HFA)

(Over-voltage/over-current input 255 counts)

B: External line abnormal detection bit

0= Normal

1=Abnormal'

: Always 0

When all data bits are 0 •• Current input line open

When all data bits are 1 •• External power is OFF

4 words occupied

(X4W)

r

XWn

CH1

XWn+1

CH2

XWn+2

CH3

XWn+3

CH4

NOTE

1. In the voltage input specification, the data bits do not become 0 when there is an open circuit

between the input terminals. (They become indeterminate between 0 and 250.)

2. It is recommended that unused channels are shorted between the input terminals.

88

Sequence Controller S2T