GF

-

128

Innovation Series Water Heaters

Appendix B

OMM-0079_0B

USER MANUAL

Display Messages

Page 96 of 200 AERCO International, Inc.

· 100 Oritani Dr. · Blauvelt, NY 10913 · Phone: 800-526-0288

07/21/11

TABLE B-2. FAULT MESSAGES

FAULT MESSAGE

FAULT DESCRIPTION

AIRFLOW FAULT

DURING PURGE

The Blower Proof Switch opened during purge,
or air inlet is blocked.

AIRFLOW FAULT

DURING IGN

The Blower Proof Switch opened during ignition.

AIRFLOW FAULT

DURING RUN

The Blower Proof Switch opened during run.

DELAYED

INTERLOCK OPEN

The Delayed Interlock is open.

DIRECT DRIVE

SIGNAL FAULT

The direct drive signal is not present or is out of range.

FFWD TEMP

SENSOR FAULT

The temperature measured by the Feed Forward
(FFWD) Sensor is out of range.

FLAME LOSS

DURING IGN

The Flame signal was not seen during ignition or lost
within 5 seconds after ignition.

FLAME LOSS

DURING RUN

The Flame signal was lost during run.

HEAT DEMAND

FAILURE

The Heat Demand Relays on the Ignition board failed to
activate when commanded.

HIGH EXHAUST
TEMPERATURE

The High Exhaust Temperature Limit Switch is closed.

HIGH GAS

PRESSURE

The High Gas Pressure Limit Switch is open.

HIGH WATER

TEMPERATURE

The temperature measured by the Outlet Sensor
exceeded the Temp Hi Limit setting.

HIGH WATER TEMP

SWITCH OPEN

The High Water Temperature Limit Switch is open.

IGN BOARD

COMM FAULT

A communication fault has occurred between the PMC
board and Ignition board.

IGN SWTCH CLOSED

DURING PURGE

The Ignition Position Limit switch on the Air/Fuel Valve
closed during purge.

IGN SWTCH OPEN

DURING IGNITION

The Ignition Position Limit switch on the Air/Fuel Valve
opened during ignition.

INTERLOCK

OPEN

The Remote Interlock is open.

LINE VOLTAGE

OUT OF PHASE

The Line (Hot) and Neutral wires are reversed.

LOW GAS

PRESSURE

The Low Gas Pressure Limit Switch is open.

LOW WATER

LEVEL

The Low Water Cutoff board is indicating low water
level.

NETWORK COMM

FAULT

The RS-485 network information is not present or is
corrupted.