beautypg.com

2 installing gas supply manometer, 3 accessing the analyzer probe port, Innovation series water heaters – AERCO Innovation (G-10-1350 to G-11-0563) User Manual

Page 42

background image

GF

-

128

Innovation Series Water Heaters

Chapter 4

OMM-0079_0B

USER MANUAL

Initial Start-Up

Page 42 of 200

AERCO International, Inc.

· 100 Oritani Dr. · Blauvelt, NY 10913 · Ph.: 800-526-0288

07/21/11

4.2.2

Installing Gas Supply Manometer

The gas supply manometer is installed in the gas train as follows:

1. Close the main manual gas supply shut-off valve upstream of the unit.

2. Remove the front door and left side panels from the heater to access the gas train components.

3. Remove the 1/8 inch NPT pipe plug from the leak detection ball valve on the downstream side of the

Safety Shut Off Valve (SSOV) as shown in Figure 4-1.

4. Install a NPT-to-barbed fitting into the tapped plug port.

5. Attach one end of the plastic tubing to the barbed fitting and the other end to the 16 inch W.C.

manometer.

Figure 4-1. 1/8 Inch Gas Plug Location

4.2.3

Accessing the Analyzer Probe Port

The unit contains a 1/8” NPT port at the rear of the exhaust manifold. This port is located above the
condensate drain connection as shown in Figure 4-2. Prepare the port for the combustion analyzer probe
as follows:

1. Refer to Figure 4-2 and remove the 1/8” NPT plug from the rear of the exhaust manifold.

2. If necessary, adjust the stop on the combustion analyzer probe so it will extend mid-way into the flue

gas flow. DO NOT install the probe at this time.