beautypg.com

Electrical power guide – AERCO Innovation (G-10-1350 to G-11-0563) User Manual

Page 180

background image

GF

-

5060

TAG-0045_0A

Electrical Power Guide

Page 180 of 200 AERCO International, Inc.

· 100 Oritani Dr. · Blauvelt, NY 10913 · Ph.: 800-526-0288

07/21/11

TERMINAL

BLOCK

UPPER RIGHT CORNER OF

FRONT PANEL

POWER

BOX

Figure 2. Terminal Block Location

Provisions for Service
Designers must provide emergency shutoffs and other devices to satisfy electrical codes. It is also
recommended to provide an electrical shutoff disconnect switch of suitable load carrying characteristics on
or near each BMK boiler. No electrical boxes or field components should be mounted to the surface of the
boiler or where they would interfere with the removal of the side or top panels for maintenance. The
disconnect switch should be mounted near the unit as illustrated in Figure 1. Wiring conduit, EMT, or other
wiring paths should not be secured to the unit, but supported externally. Electricians should be instructed as
to where the wiring conduit should be located, such as away from the relief valve discharge, drains, etc. All
electrical conduit and hardware should be installed so that it does not interfere with the removal of any
cover, inhibit service or maintenance, or prevent access between the unit and walls or another unit.

Boiler Wiring
A dedicated protected circuit should be provided from the power source to the boiler. No other electrical
devices should be permanently wired on the same circuit. An emergency switch (electrical shutoff) must be
in series with the power to the unit. Refer to Figure 3 for the wiring connections to the terminal block
contained in the unit’s Power Box.

Multiple Unit Wiring
Whenever multiple units are installed within the same mechanical spaces, electrical code requirements call
for a single electrical shutoff for emergency use. It is the responsibility of the electrical designer to comply
with local codes and regulations affecting an individual installation.

L1

GND

TERMINAL BLOCK

IN POWER BOX

DISCONNECT SWITCH
SINGLE-POLE, 20 AMP

L1

GND

120V/1/60Hz

1 POLE 20 AMP

CIR UIT BREAKER

120 VAC, 1 PHASE

NEU

NEU

Figure 3. 120V/1

Æ/60 Hz Wiring Schematic

Pg. 4 of 6