CHAPTER 6. MAINTENANCE

6.1

MAINTENANCE SCHEDULE

The Innovation Water Heater requires regular routine maintenance to ensure continued reliable operation
throughout the service life of the unit. For optimum operation, AERCO recommends that the following
routine maintenance procedures be performed in the time periods specified in Table 6-1.

Appendix I contains a list of the recommended spare parts for maintenance of the Innovation Heater.

WARNING

TO AVOID PERSONAL INJURY, PRIOR TO SERVICING ENSURE THAT THE
FOLLOWING GUIDELINES ARE STRICTLY OBSERVED:
· DISCONNECT THE AC SUPPLY BY TURNING OFF THE SERVICE

SWITCH AND AC SUPPLY CIRCUIT BREAKER.

· SHUT OFF THE GAS SUPPLY AT THE MANUAL SHUT-OFF VALVE

PROVIDED WITH THE UNIT

· ALLOW THE UNIT TO COOL TO A SAFE WATER TEMPERATURE TO

PREVENT BURNING OR SCALDING

TABLE 6-1 - MAINTENANCE SCHEDULE

PARAGRAPH

ITEM

6 Mos.

12 Mos.

24 Mos.

Labor

Time

6.2

Igniter-Injector

(58023)

*Inspect

Inspect

Replace

15 mins.

6.3

Flame Detector

(66018)

*Inspect

Inspect

Replace

15 mins.

6.4

Combustion

Calibration

*Check

Check

1 hr.

6.5

Testing of Safety

Devices

Test

20 mins.

6.6

Fireside

Inspection

Inspect &

Clean

2 hrs.

6.7

Waterside
Inspection

Inspect

1 hr.

6.8

Heat Exchanger

Cleaning

Clean

2 hrs.

6.9

Condensate

Drain Trap

*Inspect

Inspect &

Clean

30 mins.

6.10

Air Filter

(59138)

Replace

5 mins.

*

Only performed after initial 6 month period after initial startup.