beautypg.com

Innovation series water heaters – AERCO Innovation (G-10-1350 to G-11-0563) User Manual

Page 102

background image

GF

-

128

Innovation Series Water Heaters

Appendix D

OMM-0079_0B

USER MANUAL

Default Settings

Page 102 of 200 AERCO International, Inc.

· 100 Oritani Dr. · Blauvelt, NY 10913 · Phone: 800-526-0288

07/21/11

WATER HEATER DEFAULT SETTINGS - Continued

MENU & OPTION

FACTORY DEFAULT

Tuning Menu

Prop Band

8°F

Integral Gain

1.60

Derivative Time

0.10 min

Min Load Adj

0°F

Max Load Adj

0°F

FFWD Temp

N/A

Outlet Feedback

On

Feedback Gain

0.05

Breakpoint At 100%

83°F

Breakpoint At 90%

84°F

Breakpoint At 80%

85°F

Breakpoint At 70%

86°F

Breakpoint At 60%

87°F

Breakpoint At 50%

88°F

Breakpoint At 40%

92°F

Breakpoint At 30%

105°F

Breakpoint At 20%

124°F

Breakpoint At 10%

136°F

Breakpoint At 0%

138°F

Reset Defaults?

No