beautypg.com

Shutdown below freezing conditions, Actions after abnormal shutdown (fig. 26 ), Actions after power interruption – Carrier 16DF013-050 User Manual

Page 45

background image

Shutdown Below Freezing Conditions —

Begin

by shutting the machine down with Normal Shutdown
Procedure.

Then transfer most of the refrigerant into the solution:

1. Turn the burner control switch to OFF and depress the

machine Start button. Then depress the machine Stop but-
ton to start the dilution cycle.

2. Open the changeover valve ‘‘B’’ under the refrigerant tank

to drain refrigerant into the absorber.

3. After about 10 minutes, close the changeover valve ‘‘B’’.
4. The machine will stop after a dilution period of about

15 minutes.

The refrigerant circuit requires special treatment to prevent
freezing:
1. Fill a hose with water (to avoid letting air into the ma-

chine) and connect the hose between the solution pump
and refrigerant pump service valves.

2. Push machine Start button (while burner control switch

is still in the OFF position) to start the pumps.

3. Open both pump service valves for about 15 minutes. The

solution pump discharge pressure is higher so solution
will flow into the refrigerant circuit to provide antifreeze
protection.

4. Depress machine Stop button, return the burner control

switch to ON, open the control panel main circuit breaker
(MCB), and remove the transfer hose.

Completely drain all water tube bundles and flush all tubes

with an antifreeze chemical such as glycol.

Actions After Abnormal Shutdown (Fig. 26 ) —

Abnormal stop occurs automatically when any of the safety
devices sense a condition exceeding their normal safe op-
erating limit. When this happens, the fuel valve is closed,
the alarm buzzer sounds, and the machine shuts down. The
cause of the safety shutdown will be displayed in code by
the status indicator on the front of the control panel. These
codes are listed in Table 16. In case of a burner or combus-
tion failure, an alarm light on the burner control panel also
illuminates.

Some safety conditions will close the fuel valve imme-

diately, and others will first modulate the burner to the mini-
mum firing position for a normal low fire shutdown. Also,
most safety conditions will allow the normal shutdown di-
lution period but some will stop the machine immediately
without dilution. The latter conditions should be corrected
as quickly as possible to allow a restart or manual dilution
before solution crystallization can occur. See Abnormal Shut-
down in the Machine Controls section, page 29 for limit set-
tings and shutdown action for each safety type.

Take the following actions after an abnormal shutdown:

1. Identify the problem from the control panel status indi-

cator, and also from the burner control panel if it is a burner
problem.

2. Depress the machine Stop button to silence the buzzer

and to reset the control circuit for a restart after noting
the failure code.

3. Correct the cause of the problem and restart the machine

to be sure it operates normally. See Troubleshooting Guide,
pages 54 - 56 for remedies. If shutdown occurred with-
out adequate dilution, this should be done as soon as
possible.

Table 16 — Safety Devices Status

Indication Summary

INDICATION

CAUSE

SAFETY DEVICE

E01

Chilled water
low temperature

Chilled water
low temperature cutout

E02

Chilled/hot water
low flow

Flow switch
Chilled/hot water pump
interlock

E03

Cooling water
low flow

Optional Flow Switch
Cooling water pump
interlock

E04

Hermetic pumps
overload

Solution pump thermal
relay
Solution pump coil
thermostat
Refrigerant pump thermal
relay

E05

Generator high
temperature or
high pressure

High temperature
generator
pressure switch
High temperature
generator solution
temperature sensor

E06

Exhaust gas
high temperature

Exhaust gas high
temperature thermostat
Fire tube high
temperature thermostat

E07

Absorber high
temperature

Absorber solution
temperature sensor

E08

Burner — no ignition

Burner flame detector
and combustion controller

E09

Burner — misfire

Burner flame detector and
combustion controller

E10

External limit device

External emergency
stop switch
Main power failure

E12

Chilled/hot water
flow check

Flow switch,
pump interlock

E13

High-temperature
generator,
solution high level

High-temperature
generator solution
level sensor

E17

Leaving chilled/hot
water temperature

Chilled/hot water
outlet temperature
sensor

E18

Absorber solution
temperature

Absorber solution
temperature sensor

E19

High-evaporator
generator,
refrigerant temperature

High-temperature
generator, refrigerant
temperature sensor

E20

Entering chilled/
hot water
temperature

Chilled/hot water inlet
temperature sensor

E24

High-temperature
generator,
solution temperature

High-temperature
generator, solution
temperature sensor

E90

Insufficient dilution

Control circuit
power failure

Actions After Power Interruption —

If the control

power is interrupted during operation, the chiller stops im-
mediately without the normal shutdown sequence and
dilution.

Solution crystallization can occur if the concentration is

high (chiller was operating with a relatively large load). If
so, depress the Start button to restart the machine as soon as
possible after the power is restored. The machine will not
restart automatically when power is recovered. If the chiller
cannot be operated because of crystallization, follow the So-
lution Decrystallization instructions in the Maintenance Pro-
cedures section, page 53.

45