beautypg.com

Carrier 07KA User Manual

07ka, Water-cooled condensing units, Carrier

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Carrier

Start-Up and

Service instructions

07KA

Water-Cooled Condensing Units

Table 1 - Physical Data

CONDENSING UNIT 07KA

002

004

REFRIG CHG* R-22 (lb)

2 5

3.0

COMPRESSOR

Single-phase
3-phase

Oi 1 Charge! (pt)

06AD126

2

06AD228
06AC228

5

CONDENSER

T ube-in-T ube

HIGH PRESSURESTAT

Cutout
Cut-in

Fixed Differential

428 ± 5 psig

320 ± 20 psig

108 psig

LOW PRESSURESTAT

Cutout
Cut-in

Fixed Differential

30 ± 4 psig

60 ± 15 psig

30 psig

Fig. 1 - 07KA Water-Cooled Condensing Unit

*Factory charge. Refer to Refrigerant Charging, page 3,

for charging details.

tUse Carrier PP-33-2, Texaco Capella B1 or Suniso 3G

Dual Inhibited oil.

NOTE: High and low pressurestats cut-in and cutout
points are not adjustable.

Table 2 - Electrical Data (60-Cycle)

COND

UNIT

07KA

VOLTS

PHASE

NDSV

LRA

FLA

MAX

KW

WSA

BRANCH CIRCUIT

Wire

Size

(AWG No)

Max

Ft

Wire

Wire

Size

(AWG No)

Max

Ft

Wire

Fuse
Amp*

002310

230

1

230

49 0

12 0

2 75

15 2

12

46

10

74

20

004310

230

1

230

78 0

17 1

5 0

21 6

10

52

8

82

30

004510

230

3

220-
240

53 5

10 3

5 0

13 1

12

65

10

103

20

NDSV - Nominal Distribution System Voltage (Application Range) Motors and controls will operate satisfactorily 10% above

and 10% below Nominal Distribution System Voltage.

LRA - Locked Rotor Amps

FLA - Full Load Amps

WSA - Wire Sizing Amps

*Maximum dual element fuse size
NOTES:

1 Control circuit voltage is 24 volts on all units
2 Branch circuit wire sizes and corresponding maximum wire lengths tabulated will result in a 1% voltage drop at nameplate

full load amperage

START-UP INSTRUCTIONS

Crankcase heater on 07KA004 should be en­

ergized a minimum of 4 hours before starting

unit. 07KA single-phase units are of split capac­

itor (PSC) type and require an equalized system

pressure to start.

Start Procedure

1. Back-seat (open) liquid and suction line serv­

ice valves. (When accessory water regulating
valve

is

used,

"crack"

liquid

line

service

valve one-half turn from backseat position.)

2.

Open water supply valve and allow water to

reach condenser. (Water regulating valve re­
stricts

water

until

unit

is

operating.)

Open

condenser water discharge valve (when used).

3. Close disconnects energizing entire system.

4. Set room thermostat to desired temperature.
5.

Set room thermostat to "Cool" and fan switch

as desired.

Motors and controls will operate satisfactorily

10% above and 10% below nominal distribution

system voltage (see Table 2).

Carrier Corporation 1967

Printed in U.S.A.

5-67

07KA-1SS