ADS Environmental Services ADS Spider User Manual
Page 47
sending a text message to the next number on the list. It can be set
from 0 to 60 minutes.
You can exit at any time without making changes by clicking the
“
Cancel
”
link.
Save the new values by clicking on the
“
Save
”
button.
NOTES:
1. Trigger source is selected from the drop-down list. This list
will display all available inputs identified with their user-
programmed names. All unused alarms should be disabled
by selecting
“
DISABLED
”
from the list.
2. Control action may be specified as continuous or pulsed. For
example, the setting
“
Control 1 ON
”
in the continuous mode
will turn Control 1 on and leave it on. The pulsed mode will
turn Control 1 on for approximately 1 second and then turn it
off.
3. Enabling
“
Auto Acknowledge
”
will automatically acknowledge
an active alarm after a user settable amount of time. (In other
words, a user need not acknowledge the alarm manually by
sending a text message or using a browser.)
NOTE: Even with
“
Auto Acknowledge
”
enabled, the alarm will
not start sending a new series of messages unless the alarm
goes inactive as well.
4. When entering phone numbers, enter only digits. Do not
use spaces, brackets, or hyphens.
5. If you do not need all 3 telephone numbers or both e-mail
addresses, simply leave the appropriate fields blank.
6. Available trigger conditions will change depending on the
type of input used to trigger the alarm. For example, while
switch (or digital) inputs can trigger on the
“
ON STATE
”
or the
“
OFF STATE
”
, analog inputs will allow triggering on