Alarms – ADS Environmental Services Spider QR 775010 A0 User Manual
Page 16

ADS Environmental Services ADS Spider User Manual
Page 14
a dedicated 7-day, 24-hour timer with an unlimited number of user-
programmable schedules.
The user can tailor the system by assigning application-specific
names to the controls. For example, Control 3 may become
“
VALVE
4 ON
”
.
Controls can be managed in four ways:
1. By accessing the
“
Controls
”
page with a browser and clicking
the ON/OFF buttons
2. By sending control text messages to the unit
3. By programming and enabling the timer
4. By programming alarms to activate or deactivate controls
It is possible to use all four forms of control simultaneously. If a timer
is enabled and a manual control command is received through either
the browser or a text message, the manual control will take priority,
temporarily overriding the timer. The override is automatically
cancelled when the programmed timer state matches the manually
requested state.
Controls driven by an alarm have the highest priority, overriding both
manual control and the timer. Furthermore, if two or more alarms
attempt to drive a control in opposite states, the
“
OFF
”
command will
override the
“
ON
”
command.
Alarms
The ADS Spider can generate up to 8 alarms.
Upon activation, an alarm can perform any or all of the following:
Send text messages
Send e-mails (if e-mail option installed)
Dial any telephone and communicate the alarm message in a
synthesized voice
Activate and deactivate controls
Each alarm can be programmed with a name, a trigger source, 3
separate text message telephone numbers, 2 e-mail addresses, 3
separate voice numbers, the text of a message, and the control to be