beautypg.com

Appendix d, Recommended float and equalize voltages – Exide Technologies Section 94.40 User Manual

Page 94

background image

APPENDIX D

90

RECOMMENDED FLOAT AND EQUALIZE VOLTAGES

This table contains suggested values for commonly used batteries. Consult your battery
manufacturer's documentation for specific values and settings for your battery type.

Battery Cell Type

Recommended

Float Voltage/cell

Recommended

Equalize Voltage/cell

Antimony (1.215 Sp. Gr.)

2.17

2.33

Antimony (1.250 Sp. Gr.)

2.20

2.33

Selenium (1.240 Sp. Gr.)

2.23

2.33 - 2.40

Calcium (1.215 Sp. Gr.)

2.25

2.33

Calcium (1.250 Sp. Gr.)

2.29

2.33

Lead

-Acid Types

Absorbed / Gelled Electrolyte *

(sealed lead acid type)

2.25

*

Nickel Cadmium

1.42

1.47

* Sealed lead-acid battery types should not be used in ambient temperatures above 95°
F / 35° C, and should not normally be equalized. Consult your battery manufacturer's
documentation for specific equalizing recommendations.


TEMPERATURE COMPENSATION

If batteries are to see temperature variations during charging, a temperature
compensation option (A10) is recommended. If this option is not part of your charger,
manual adjustments should be made. Refer to the equation and table below for
temperature-adjusted voltages.

temperature-adjusted voltage = charge voltage x K

Temperature

(°F)

Temperature

(°C)

K

(Lead Acid)

K

(Nickel Cadmium)

35

1.7

1.058

1.044

45

7.2

1.044

1.034

55

12.8

1.031

1.023

65

18.3

1.017

1.013

75

23.9

1.003

1.002

77

25.0

1.000

1.000

85

29.4

0.989

0.992

95

35.0

0.975

0.981

105

40.6

0.961

0.970