OPERATING THE AT30
36
2.3.6. Enabling the High DC Voltage shutdown feature
The AT30 has a built-in high dc voltage shutdown feature. In case of any
maladjustment or internal failure that results in a continuous output
voltage that is too high, the AT30 shuts down after 30 seconds to protect
the battery. The digital display shows
E 03, and the summary alarm relay
contact transfers.
The AT30 is shipped with the high dc voltage shutdown feature disabled.
You can adjust the high dc voltage shutdown
(the setting is the same as the high dc voltage
alarm setting). Refer to Section 2.3.4.
The charger must be in normal operation (not
the Edit mode) to enable the high dc voltage
shutdown.
To enable the shutdown feature:
•
Press and hold the
UP
key, then
•
Press the
CHRG MODE
key.
The
HIGH DC VOLTAGE
indicator lights, and
the display flashes
ON. You can toggle the
shutdown feature
OFF and ON by pressing the
CHRG MODE
key repeatedly.
Parallel Operation
If two (or more) AT30
chargers are connected in
parallel, both sense the
output voltage. If one
charger runs away, it will
supply all the output
current; the other has zero
output current. The high dc
voltage shutdown does not
operate in a charger with
zero output current, so that
only the defective charger
(of two or more in parallel)
shuts down. The other
charger continues to supply
the load normally.
If you do not press any key within 4 seconds, the last state indicated (
ON
or
OFF) is saved internally. Note that you do not use the
EDIT/ENTER
key
for this feature.
If the AT30 shuts down because of a high dc voltage, the meter display
shows error code
E 03. Reset the charger by turning the ac breaker off,
then on again.