INSTALLING THE AT30

19

Auxiliary Relay Board (optional)

The optional Auxiliary Alarm Relay PC Board (A5), mounted on plastic
stand-offs inside the enclosure, provides two (2) form-C contacts (TB4-1
through TB4-36) for each of the following individual alarms:

High DC Voltage

Low DC Voltage

DC Output Failure

AC Input Failure

Ground Fault Detection (positive or negative)

Summary (common) Alarm

Alarm contacts (TB4) are as follows, shown in non-alarm condition:

HVDC

HVDC

LVDC

LVDC

DC OUT

FAILURE

DC OUT

FAILURE AC FAIL

AC FAIL

GROUND

DETECT

GROUND

DETECT SUMMARY SUMMARY

C, NC, NO C, NC, NO C, NC, NO C, NC, NO C, NC, NO C, NC, NO C, NC, NO C, NC, NO C, NC, NO C, NC, NO C, NC, NO C, NC, NO

1 2 3

4 5 6

7 8 9

10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

PROCEDURE
1. Deenergize and lock out all ac and dc voltages to the AT30.

2. Allow internal voltages to dissipate, then check with a voltmeter.

3. Remove the plexiglas safety shield, if supplied.

4. Route your remote annunciator wiring into the enclosure through one of the

unused conduit knockouts on the side of the enclosure.

5. Connect the wiring (use #22-14 AWG) to the appropriate terminals of TB4

on the Auxiliary Alarm Relay board (as shown in the figure above). Strip
each wire 0.25in / 6.4mm and securely tighten the terminal screws.

6. Replace the safety shield, if supplied, and restart the AT30.
NOTES
1. Alarm contacts are rated at 0.5A / 125 Vac or Vdc.

2. Terminal block (TB4) is compression type, accepting #22-14 AWG wire.

3. Terminals are labeled in non-alarm condition.

4. For a detailed view of the optional Auxiliary Alarm Relay PC Board (A5),

refer to drawing (

JE5091-39

) listed in Appenix C on Page 78.