Servicing the at30 – Exide Technologies Section 94.40 User Manual
Page 61

SERVICING THE AT30
57
SYMPTOM PROBABLE
CAUSE
RECOMMENDED ACTION
AC INPUT 
FAILURE 
indicator is on 
1. AC power 
failure 
2. Upstream 
feed 
breaker/fuse is 
tripped 
3. Defective 
wiring 
4. Defective 
Main Control 
board A1 
1. If the ac input power fails, the front panel
AC ON indicator goes
out, and the
AC INPUT FAILURE indicator goes on.
2. Be sure the front panel ac circuit breaker (CB1) is closed. 
Measure the ac voltage at the AT30 input terminals (TB1-L1, TB1-
L2 and TB1-L3). If it is zero, check the upstream distribution 
breakers and fuses. 
3. Measure ac voltage at the transformer primary taps (T1-H1, T1-
H2 & T1-H3). It should be the same as the ac supply voltage. 
4. Turn off both front panel circuit breakers (CB1/CB2), or turn off 
ac and dc power externally, if the AT30 does not have breakers. 
Wait one minute before returning the dc connection, followed by 
the ac connection. If the 
AC ON indicator is on, but the AC INPUT
FAILURE indicator is still on, replace the Main Control board (A1).
POS GND or 
NEG GND 
indicator is on 
1. Ground fault 
on external dc 
bus 
2. DC circuit 
breaker is open 
and 
NEG GND
indicator is on
3. Alarm needs 
calibration 
4. Defective 
wiring 
 
 
 
 
 
 
 
 
 
5. Defective 
Main Control 
board A1 
1. Disconnect the AT30 from the battery and dc bus, and check 
the battery and dc bus for a ground fault. 
 
3. If the AT30 has been placed into standby by opening the dc 
breaker (CB2), the ground detection circuit gives an erroneous 
alarm. Close the dc breaker and the alarm should end. If you want 
the AT30 to be in standby, open the ac circuit breaker (CB1). 
3. Calibrate ground detection sensitivity. See Section 2.3.4.
 
4. Turn off both front panel circuit breakers (CB1/CB2), or turn off 
ac and dc power externally, if the AT30 does not have breakers. 
Wait one minute and disconnect the AT30 from the battery and dc 
bus. Turn on the AT30 and measure the voltage from TB1(+) to 
chassis, and from TB1(-) to chassis. The voltage readings should 
be equal, each approximately half of the total output voltage. If 
there is more than a 10% imbalance, turn the AT30 off and 
inspect all wiring from TB1 to the dc circuit breaker (CB2), and the 
rectifier bridge to the dc filter inductor (L1). Look for evidence of 
insulation damage, insufficient spacing between terminals and 
chassis, or wires run too close to metal edges. 
5. Turn off both front panel circuit breakers (CB1/CB2), or turn off 
ac and dc power externally, if the AT30 does not have breakers. 
Wait one minute before returning the dc connection, followed by 
the ac connection. If you are sure there is no ground fault on the 
external bus or within the charger, but the 
POS GND or NEG
GND indicator is still on, replace the Main Control board (A1).
Summary 
alarm relay is 
in alarm 
mode, but no 
front panel 
alarm indicator 
is on 
1. Defective 
Main Control 
board A1 
1. Turn off both front panel circuit breakers (CB1/CB2), or turn off 
ac and dc power externally, if the AT30 does not have breakers. 
Wait one minute before returning the dc connection, followed by 
the ac connection. If the relay remains in alarm mode, check the 
Low Level Detect indicator on Main Control board (A1). See 
Section 2.3.8. If no other alarm is on, replace the Main Control 
board (A1). 
