Operating the at30 – Exide Technologies Section 94.40 User Manual
Page 33

OPERATING THE AT30
29
2.2.5. Testing the front panel indicators
•
Press the
DOWN
key. This is also the
LAMP TEST
key.
The meter will display
8888
, and all status & alarm indicators will light.
The
LAMP TEST
key does not test the
AC ON
indicator. The
AC ON
indicator lights whenever ac power is present, and the ac circuit breaker is 
turned on. The 
LAMP TEST
key does not operate when ac power is off.
To test the action of the AT30 summary alarm relay, press and hold the
LAMP TEST
key for four seconds to transfer the relay. If you are monitoring
the relay with a remote annunciator, it will detect the alarm condition.
2.2.6. Testing the Auxiliary Relay Board (optional)
If you have the optional Auxiliary Relay Board (A5) installed, you can 
similarly test the six individual alarm relays. Press and hold the 
LAMP TEST
key for four seconds to transfer the relays. If you are monitoring the 
relays with a remote annunciator, it will detect the alarm conditions. 
2.2.7. Interpreting the alarm indicators
There are six red alarm indicators at the right side of the front panel. An 
indicator lights for each of the following alarm conditions: 
•
HIGH DC VOLTAGE: lights whenever the dc output voltage exceeds the 
specified alarm voltage setting. See Section 2.3.4 to learn how to adjust the 
HVDC alarm setting. 
•
LOW DC VOLTAGE: lights whenever the dc output voltage is below the 
specified alarm voltage setting. See Section 2.3.4 to learn how to adjust the 
LVDC alarm setting. 
•
DC OUTPUT FAILURE: lights whenever the charger cannot provide its full 
rated output voltage 
or its full rated output current. You cannot adjust this
alarm setting.
•
AC INPUT FAILURE: lights whenever the ac power supply to the charger is 
interrupted. 
•
POS GND: lights whenever leakage current from the battery positive terminal 
to ground exceeds a specified threshold. 
•
NEG GND: lights whenever leakage current from the battery negative terminal 
to ground exceeds a specified threshold. 
NOTE: You can adjust the sensitivity of the ground fault detection 
from 5K to 50k ohms. Adjusting the ground fault sensitivity affects 
the positive and negative ground fault sensitivities equally. 
When an alarm occurs, the indicators will light immediately. The AT30 
also features a summary alarm relay with one form-C contacts (TB3) rated 
0.5A / 125 Vac/Vdc. If an alarm condition lasts for 30 seconds or longer, 
the summary alarm relay transfers. Under standard settings, when the 
alarm condition is corrected, the corresponding relay and indicator resets 
automatically. Latching alarm capability for the AT30 battery charger is 
available, featured in a supplemental document (
JA5098-00
).
