Servicing the at30 – Exide Technologies Section 94.40 User Manual
Page 57

SERVICING THE AT30
53
SYMPTOM PROBABLE
CAUSE
RECOMMENDED ACTION
Output 
voltage does 
not agree 
with front 
panel meter 
1. Temperature 
compensation 
probe is 
installed 
 
2. Circuit board, 
or another 
component may 
have been 
replaced 
3. R4 or R14 is 
defective, or 
wrong value 
 
 
4. Defective 
Main Control 
board A1 
1. If the optional temperature compensation probe is installed, 
the output voltage may be different from the selected float or 
equalize voltage. The difference in the voltages depends on 
the probe temperature. The front panel meter always displays 
the selected voltage as if the battery were at 77° F / 25° C. 
2. Recalibrate the voltmeter accuracy as described in Section 
2.3.7. 
 
 
 
3. See page 61 of Section 3.5. Locate R4 and R14 on the 
Gate Driver pc board (A15). Remove one end of each resistor 
and measure its value with an Ohmmeter. See the table in 
Section 3.6 for resistance values. If either resistor is not within 
1% of the specified value, replace R4 and/or R14 as needed. 
4. Turn off both front panel circuit breakers (CB1/CB2), or turn 
off ac and dc power externally, if the AT30 does not have 
breakers. Wait one minute before returning the dc connection, 
followed by the ac connection. If the charger still has the 
wrong output voltage, replace the Main Control board (A1). 
Charger 
never 
reaches float 
(or equalize) 
voltage 
(within 1%) 
1. Current limit 
set too low 
 
 
 
2. Defective 
battery or dc 
load, or load is 
too great 
3. Wrong ac 
input voltage, or 
voltage too low, 
or T1 wired 
incorrectly 
4. Defective 
rectifier bridge 
 
 
5. Defective 
Main Control 
board A1 
1. If the AT30 is not in the Edit mode, press the
EDIT/ENTER
key five times, until the meter display flashes the current limit 
value (in Amperes). If the current limit is less than 110%, 
adjust it to 110% as described. See 
Setting the Current Limit
Value, Section 2.3.5 for details. 
2. Check each cell of the battery. If one or more cells are 
shorted, the AT30 may not be able to reach the Float voltage. 
You may have the same problem if the normal load current is 
more than the rated output current of the charger. 
3. Be sure the main transformer (T1) primary taps are wired 
correctly for your input voltage. See 
Changing Transformer
Taps, Section 1.6. The actual ac input voltage must be at least 
88% of the rated value for the AT30 to produce full output 
power. 
4. Use a clamp-on ammeter to measure the current in wires # 
7, 8 & 9, between T1 and the rectifier modules. If it less than 
50% of the dc output current, one of the SCRs or diodes is 
defective. Replace the rectifier module(s) (A16) as needed. 
5. Turn off both front panel circuit breakers (CB1/CB2), or turn 
off ac and dc power externally, if the AT30 does not have 
breakers. Wait one minute before returning the dc connection, 
followed by the ac connection. If the charger output current is 
below the current limit value, but it still has the wrong output 
voltage, replace the Main Control board (A1). 
