Servicing the at30, Symptom probable cause recommended action – Exide Technologies Section 94.40 User Manual
Page 54

SERVICING THE AT30
50
SYMPTOM PROBABLE
CAUSE
RECOMMENDED ACTION
DC breaker 
trips (or fuses 
clear) 
immediately 
1. Battery 
connected with 
reverse polarity 
2. Defective 
rectifier bridge (if 
unfiltered AT30) 
 
 
 
3. Defective 
Free-Wheeling 
diode CR4 
 
 
 
4. Defective 
Polarity Diode 
CR1 (if filter 
assembly is 
installed) 
 
5. Defective 
wiring 
1. Check and correct battery wiring if necessary. 
 
 
2. Test by disconnecting wires #
7, 8 & 9 at the rectifier module(s)
(A16) mounted on the main heat sink(s), or at the main 
transformer (T1). Measure resistance between the ac terminals 
(bottom terminals) on the rectifier module(s). It should be at least 
100,000 Ohms (check both polarities). If resistance is low in either 
direction, replace the rectifier module(s) (A16) as needed. 
3. Disconnect wire #
15 from SCR module mounted on the heat
sink assembly or from the positive bus bar. Measure the 
resistance through the Free-Wheeling diode (CR4). Check both 
polarities; it should be at least 100,000 Ohms in one polarity, and 
less than 1,000 Ohms in the other polarity. Replace CR4 if it is 
defective. 
4. Disconnect wire #
17 from the dc circuit breaker (CB2), or the
optional dc fuse (F3). Measure the resistance through the Polarity 
Diode (CR1), mounted to the 
negative filter capacitor bus bar.
Check both polarities. It should be at least 100,000 Ohms in one 
polarity, and less than 1,000 Ohms in the other polarity. Replace 
CR1 if it is defective. 
5. Check spacing of terminals and check wiring for signs of 
insulation damage, burns, etc. Repair as necessary. 
DC breaker 
trips (or fuses 
clear) after a 
few minutes 
1. Loose 
connection to 
breaker 
2. Open SCR 
 
 
 
3. SCR not 
controllable 
 
 
4. Defective 
Gate Driver pc 
board board A15 
 
5. Defective 
Main Control 
board A1 
1. Check and tighten connections as required. 
 
 
2. Use a clamp-on ammeter to measure the current in wires #
7, 8
&
9, between T1 and the rectifier modules. If it less than 50% of
the dc output current, one of the SCRs or diodes is defective. 
Replace the rectifier module(s) (A16). 
3. Disconnect the wire harness plug from connector J26 on the 
top of the Gate Driver pc board (A15) and restart the AT30. If you 
are able to measure output current, one of the SCRs is defective. 
Replace the rectifier module(s) (A16) as needed. 
4. If the front panel meter shows more than 110% of rated dc 
current, the Gate Driver pc board (A15) may be defective. Unplug 
A15 from the Main Control board (A1). If the output current 
DOES
NOT drop to zero, replace the Gate Driver pc board (A15). 
5. If the front panel meter shows more than 110% of rated dc 
current, the Main Control board (A1) may be defective. Unplug the 
system harness connectors (J25 and J26) from the Gate Driver pc 
board (A15). If the output current drops to zero, replace the Main 
Control board (A1). 
