OPERATING THE AT30

27

2.2.3. Selecting the Float or Equalize mode

The AT30 has 2 output voltage settings, Float and Equalize. Use the Float
mode for all normal battery charging and to operate your dc system. Use
the Equalize mode if it is necessary to balance the level of charge among
the cells of the battery. Consult your battery data sheets for information on
equalize charging your battery.

Press the

CHRG MODE

key to change to the equalize mode.

If the equalize method is set to manual timer or auto-equalize timer, the
charger will revert to the float mode at the end of the selected equalize
time.

You can press the

CHRG MODE

key again at any time to change back to the

float mode.

2.2.4. Choosing the Equalize method

Press the

EQLZ MTHD

key to choose the desired equalize method. The

indicator next to the desired equalize method will light. Three equalize
methods are available in the AT30:

Manual Timer

Manual Equalize

Auto-Equalize Timer

These equalize methods are described below.

Manual Timer Method

Choose the manual timer method if you perform regularly scheduled
equalize charging, or if you base your equalize charging on regular
readings of the specific gravity of each cell of your battery (for lead-acid
batteries). When your battery requires equalize charging, adjust the
manual timer to 1-2 hours for each 100 AH of battery capacity (see
Section 2.3.3 to learn how to adjust the equalize time). The battery
manufacturer can help you determine the best equalizing schedule for
your battery.

After you select the manual timer method, press the

CHRG MODE

key to put

the charger into the equalize mode. The

EQLZ

indicator will light. When

the equalize timer is finished, the charger reverts automatically to the float
mode, and the

FLOAT indicator lights.

At any time during the equalize charge, you can switch the charger back
to float mode by pressing the

CHRG MODE

key. The

FLOAT

indicator will

light.

If there is an ac power failure during the equalize charge, the AT30
remembers the remaining equalize time. When ac power is restored, it
resumes the equalize charge where it left off.