Operating the at30 – Exide Technologies Section 94.40 User Manual
Page 34

OPERATING THE AT30
30
2.3. SETTING PARAMETERS IN THE AT30
2.3.1. Understanding Parameter Settings
You can change the settings of the AT30 while the charger is operating,
using the front panel controls. The changes you make take effect
immediately, and are saved internally. If the charger is taken out of
service, and then later returned to service, it restarts using the last values
you set. You can adjust the following parameters:
•
Float voltage
•
Equalize voltage
•
Equalize timer (in hours)
•
High dc voltage alarm setting
•
Low dc voltage alarm setting
•
Current limit value (in Amperes)
•
High dc voltage shutdown feature (on or off)
Your choice of equalize method is also saved internally.
When you want to change any parameter, press the
EDIT/ENTER
key to put
the AT30 into
Edit mode. The meter display flashes about once per
second, and the status indicators prompt you to adjust the respective
parameter. You adjust each parameter by pressing the
UP
or
DOWN
key
until the reading you want shows on the meter display. You can make the
display scroll up or down continuously by pressing and holding the
UP
or
DOWN
key.
You cannot exceed certain upper and lower limits for the operating
parameters. To see what the limits are for your charger, refer to the AT30
Specifications in Appendix A on page 64.
When you first press the
EDIT/ENTER
key, the AT30 prompts you to adjust
the first parameter in the list above (float voltage). When you obtain the
value you want on the display, press the
EDIT/ENTER
key again. The AT30
saves the new setting internally, and then prompts you to adjust the
second parameter. You continue this way to adjust the first six parameters
in the list above. If you want to skip adjusting any parameter, just press
the
EDIT/ENTER
key again. The AT30 moves to the next parameter.
When you are finished adjusting the sixth parameter (current limit), press
the
EDIT/ENTER
key again. The AT30 saves all adjustments you made
internally, and reverts to normal operation. The new settings take effect
immediately.
Edit mode ends automatically if you do not press any front panel key
within 25 seconds, and any change you made to the last setting is not
saved.