INSTALLING THE AT10.1
4
1.5.1. Wall-Mounting the AT10.1
In planning for wall mounting of the AT10.1 consider the following:
1. Wall-mounting the Style-5017 enclosure is standard. If you are wall-
mounting a charger in the Style-5018 enclosure, you need the wall mounting
bracket kit (part number
EI5008-00). For kit availability see ordering
information in Appendix B on page 71. The kit includes dimensions and
instructions for locating the wall mounting holes.
2. The wall must be strong enough to properly support the weight of the
AT10.1. The weight of your AT10.1 may be different from the table value,
depending on options or accessories you ordered. See the Weight Table
located in
Section
1.4 on page 3.
3. Placement of conduit entrances. Note the standard pre-fab conduit
knockouts located on the sides of the charger. See outline drawings in
Appendix C.
4. The location:
•
Should be free of drips and splatter. If dripping liquids are a problem,
install a drip shield kit. For kit availability see ordering information in
Appendix B on page 71.
•
Should be between 32 and 122 °F / 0 and 50 °C, with relative humidity
between 5 and 95% non-condensing.
•
Must be free of flammable or explosive materials.
5. Maintain at least 6in / 152mm of free air on top, bottom and both sides for
cooling air.
6. Allow 36in / 914mm front clearance for access to the charger for operation
and maintenance.