INSTALLING THE AT10.1

18

1.10. WIRING TO THE REMOTE ALARM CONTACTS

Built-in Summary (Common) Alarm Relay (standard)

The Main
Control PC
Board (A1),
mounted on the
back of the
front door, is
equipped with
one form C
Summary
Alarm contact
(TB3) that
transfers for
any alarm.

Follow the
procedure
below to wire
an annunciator
to this contact.
See Section
2.2.7 for a
description of
the alarm
functions.

PROCEDURE
1. Allow 30in / 762mm of wire inside the enclosure (excess will be trimmed).

2. Route wires to front door by following the existing harness through the door

hinge as shown. Use (2) wire ties and allow a 4-6in / 102-153mm loop for
the hinge.

3. Trim wires to the proper length for connecting to TB3. Strip 0.25in / 6.4mm

of insulation from the wires. Make the connections at TB3, and securely
tighten the screws.

NOTES
1. Alarm contacts are rated at 0.5A / 125 Vac/Vdc.

2. Terminal block is a compression type, accepting wire sizes #22-14 AWG.

3.

Terminals are labeled in non-alarm condition.