OPERATING THE AT10.1

33

Setting the High DC Voltage Alarm

Press the

EDIT/ENTER

key until the

HIGH DC VOLTAGE indicator

flashes, and the display flashes the present value of the high dc voltage
alarm.

Press and release the

UP

or

DOWN

key to increase or decrease the value in

the display by one count, or press and hold the

UP

or

DOWN

key to scroll

the value in the display upward or downward. When the display shows the
high dc voltage alarm point that you want to set, release the

UP

or

DOWN

key. If you go past the voltage you want, press the

UP

or

DOWN

key again

to reach the voltage you want to set.

Press the

EDIT/ENTER

key. The new high dc voltage alarm setting is

entered into permanent memory.

Setting the low DC Voltage Alarm

Press the

EDIT/ENTER

key until the

LOW DC VOLTAGE indicator

flashes, and the display flashes the present value of the low dc voltage
alarm.

Press and release the

UP

or

DOWN

key to increase or decrease the value in

the display by one count, or press and hold the

UP

or

DOWN

key to scroll

the value in the display upward or downward. When the display shows the
low dc voltage alarm point that you want to set, release the

UP

or

DOWN

key. If you go past the voltage you want, press the

UP

or

DOWN

key again

to reach the voltage you want to set.

Press the

EDIT/ENTER

key. The new low dc voltage alarm setting is

entered into permanent memory.

If you want to adjust the current limit setting, skip to Section 2.3.5.

OR

If you want to exit the Edit mode now, press the

EDIT/ENTER

key again to

return the charger to normal operation.