beautypg.com

Installing the at10.1 – Exide Technologies Section 94.30 User Manual

Page 10

background image

INSTALLING THE AT10.1

6

1.5.2. Floor-Mounting the AT10.1

To floor mount the AT10.1, you must consider the following:

1. Floor-mounting the Style-5018 enclosure is standard. If you are floor

mounting a charger in the Style-5017 enclosure you will need the floor-
mount kit (part number

EI0192-00). For kit availability see ordering

information in Appendix B on page 71. The kit contains brackets that elevate
the top of the AT10.1 approximately 47in / 1194mm above floor level, with
provisions for floor anchoring. The kit includes dimensions and instructions
for locating the floor mounting holes.

2. Placement of conduit entrances. Note the standard pre-fab conduit

knockouts located on the sides of the charger. See outline drawings in
Appendix C.

3. The location:

Should be free of drips and splatter. If dripping liquids are a problem,
install a drip shield. See ordering information in Appendix B on page 71.

Should be between 32 and 122 °F / 0 and 50 °C, with relative humidity
between 5 and 95% non-condensing.

Must be free of flammable or explosive materials.

4. Maintain at least 6in / 152mm of free air on top, bottom and both sides for

cooling air.

5. Allow 36in / 914mm front clearance for access to the charger for operation

and maintenance.