INSTALLING THE AT10.1
6
1.5.2. Floor-Mounting the AT10.1
To floor mount the AT10.1, you must consider the following:
1. Floor-mounting the Style-5018 enclosure is standard. If you are floor
mounting a charger in the Style-5017 enclosure you will need the floor-
mount kit (part number
EI0192-00). For kit availability see ordering
information in Appendix B on page 71. The kit contains brackets that elevate
the top of the AT10.1 approximately 47in / 1194mm above floor level, with
provisions for floor anchoring. The kit includes dimensions and instructions
for locating the floor mounting holes.
2. Placement of conduit entrances. Note the standard pre-fab conduit
knockouts located on the sides of the charger. See outline drawings in
Appendix C.
3. The location:
•
Should be free of drips and splatter. If dripping liquids are a problem,
install a drip shield. See ordering information in Appendix B on page 71.
•
Should be between 32 and 122 °F / 0 and 50 °C, with relative humidity
between 5 and 95% non-condensing.
•
Must be free of flammable or explosive materials.
4. Maintain at least 6in / 152mm of free air on top, bottom and both sides for
cooling air.
5. Allow 36in / 914mm front clearance for access to the charger for operation
and maintenance.