Operating the at10.1 – Exide Technologies Section 94.30 User Manual
Page 35
OPERATING THE AT10.1
31
2.3.2. Setting the Float and Equalize voltages
•
Press the
EDIT/ENTER
key.
The
FLOAT
and
DC VOLTS
indicators light, and the display flashes the
present value of the float voltage. Press and release the
UP
or
DOWN
key to
increase or decrease the value in the display by one count, or press and
hold the
UP
or
DOWN
key to scroll the value in the display upward or
downward. When the display shows the float voltage you want to set,
release the
UP
or
DOWN
key. If you go past the voltage you want, press the
UP
or
DOWN
key again to reach the voltage you want to set.
•
Press the
EDIT/ENTER
key. The new float voltage setting is saved
internally.
The
EQLZ and DC VOLTS
indicators light, and the display flashes the
present value of the equalize voltage. Press and release the
UP
or
DOWN
key to increase or decrease the value in the display by one count, or press
and hold the
UP
or
DOWN
key to scroll the value in the display upward or
downward. When the display shows the equalize voltage you want to set,
release the
UP
or
DOWN
key. If you go past the voltage you want, press the
UP
or
DOWN
key again to reach the voltage you want to set.
•
Press the
EDIT/ENTER
key. The new equalize voltage setting is saved
internally.
If you want to adjust the equalize timer duration, skip to Section 2.3.3.
OR
If you want to exit the Edit mode now, press the
EDIT/ENTER
key four more
times until the charger returns to normal operation.
Edit mode ends automatically if you don't press any front panel key within
25 seconds, and any change you made to the last setting is not saved.