beautypg.com

Operating the at10.1 – Exide Technologies Section 94.30 User Manual

Page 35

background image

OPERATING THE AT10.1

31

2.3.2. Setting the Float and Equalize voltages

Press the

EDIT/ENTER

key.

The

FLOAT

and

DC VOLTS

indicators light, and the display flashes the

present value of the float voltage. Press and release the

UP

or

DOWN

key to

increase or decrease the value in the display by one count, or press and
hold the

UP

or

DOWN

key to scroll the value in the display upward or

downward. When the display shows the float voltage you want to set,
release the

UP

or

DOWN

key. If you go past the voltage you want, press the

UP

or

DOWN

key again to reach the voltage you want to set.

Press the

EDIT/ENTER

key. The new float voltage setting is saved

internally.

The

EQLZ and DC VOLTS

indicators light, and the display flashes the

present value of the equalize voltage. Press and release the

UP

or

DOWN

key to increase or decrease the value in the display by one count, or press
and hold the

UP

or

DOWN

key to scroll the value in the display upward or

downward. When the display shows the equalize voltage you want to set,
release the

UP

or

DOWN

key. If you go past the voltage you want, press the

UP

or

DOWN

key again to reach the voltage you want to set.

Press the

EDIT/ENTER

key. The new equalize voltage setting is saved

internally.

If you want to adjust the equalize timer duration, skip to Section 2.3.3.

OR

If you want to exit the Edit mode now, press the

EDIT/ENTER

key four more

times until the charger returns to normal operation.

Edit mode ends automatically if you don't press any front panel key within
25 seconds, and any change you made to the last setting is not saved.