Operating the at10.1, Suggested frequency: every 6 months – Exide Technologies Section 94.30 User Manual
Page 46
OPERATING THE AT10.1
42
SAMPLE PREVENTIVE MAINTENANCE PROCEDURE
AT10.1 BATTERY CHARGER
Suggested frequency: every 6 months
Maintenance date
Performed by
Step
(standard features)
Instructions
Results
Clean battery
charger
•
All vents clean and open.
•
Remove dust and debris from inside of
unit.
o
OK
o
OK
Check all
electrical
connections
and wiring
•
TB1 connections all tight.
•
Internal wiring connections tight, slip-on
connectors fully seated. Wire and lug
insulation in good condition.
•
Terminations at battery or bus are tight
and corrosion free.
o
OK
o
OK
o
OK
Check ac input
voltage
•
Measure between TB1-L1 and TB1-L2
using an ac voltmeter. Value must be
within +10%, -12% of nominal voltage.
Input
Vac
Check dc
output voltage
•
Measure at TB1(+) and TB1(-) using a dc
voltmeter. Value should agree with front
panel voltmeter within +/-
0.25
%, and
must be correct values for your battery. If
the AT10.1 is using a temperature
compensation probe, see the graph on
page 23 to determine correct battery
voltage. You need to know the battery
temperature for this step.
Float
Vdc
Equalize
Vdc
Check ripple
voltage
•
Measure at battery terminals using an ac
voltmeter set to the milliVolts scale.
Check against specification in Appendix
A on page 70.
Ripple
mVac
Test font panel
indicators
•
Press
LAMP TEST
key on front panel.
o
OK
Test common
alarm relay
•
Press
LAMP TEST
key and hold for 4
seconds. Common alarm relay will
transfer.
o
OK