Servicing the at10.1, Symptom probable cause recommended action – Exide Technologies Section 94.30 User Manual
Page 59

SERVICING THE AT10.1
55
SYMPTOM PROBABLE
CAUSE
RECOMMENDED ACTION
Lamp test key 
does not work, 
or some lamps 
do not light 
1. No Vac
2. Control circuit 
board A1 is not 
secured to front 
panel 
3. Defective 
Main Control 
board A1 
1. The lamp test key doesn’t work during an ac power failure.
2. Open the front panel, and be sure that the control circuit board 
is securely mounted on the standoffs on the back of the panel. All 
indicators should extend about 0.125in / 3.18mm through the front 
of the panel. 
3. When you press the
LAMP TEST key, if some but not all
indicators light, or the digital meter does not display "
8888",
replace the Main Control board (A1).
One or more 
front panel 
keys don't 
work 
1. Front panel is 
locked 
2. Main Control 
board A1 is not 
secured to front 
panel 
3. Defective 
Main Control 
board A1 
1. Open the front panel, and be sure that jumper (J9) on the Main 
Control board (A1) is in the 
ENABLE position.
2. Open the front panel, and be sure that the control circuit board 
is firmly seated on the standoffs on the back of the panel. Front 
panel keys must operate freely. 
 
3. Turn off both front panel circuit breakers (or turn off ac and dc 
power externally if the charger doesn’t have breakers). Then turn 
on the dc breaker, followed by the ac breaker. If some of the front 
panel keys still do not work, replace the Main Control board (A1). 
Two AT10.1s 
connected in 
parallel, but 
only one has 
output current 
1. If the forced 
load sharing 
option is not 
supplied, check 
for normal 
operation of 
both chargers 
 
2. EJ5126-## 
option 
1. Multiple AT10.1s are not designed to share load current, 
without the optional forced load sharing cable installed. When 
two or more AT10.1s are connected in parallel without this option, 
it is normal for one of the units to have no output current. You can 
check the operation of the "off" charger by increasing its Float 
voltage until it starts to deliver output current. When you have 
finished the test, be sure both AT10.1s are set to the same Float 
and Equalize voltages. 
2. See Appendix F on page 92 for troubleshooting of Forced Load 
Sharing feature. 
HIGH DC 
VOLTAGE 
indicator is on 
1. HDCV alarm 
and Equalize 
voltage settings 
are mismatched 
2. Defective 
rectifier bridge 
 
 
 
3. Defective 
Main Control 
board A1 
 
1. Be sure that the High DC Voltage alarm setting is higher than 
the Equalize voltage setting. See Sections 2.3.2 and 2.3.4. 
 
 
2. Disconnect wires # 
51/52 and # 53/54 from the SCR gate lead
terminals (these are small gauge twisted pairs). Be sure to note 
original polarity, so they can be replaced with the same polarity. 
Restart the charger. If You are able to measure output current, 
one of the SCRs is defective. Replace the rectifier modules. 
3. Turn off both front panel circuit breakers (or turn off ac and dc 
power externally if the charger doesn’t have breakers). Then turn 
on the dc breaker, followed by the ac breaker.. If the charger 
output voltage is normal, but the 
HIGH DC VOLTAGE indicator is
still on, replace the Main Control board (A1).
No alarm, but 
output voltage 
is above High 
DC Voltage 
setting 
1. Output current 
is below 2% 
 
2. Defective 
Main Control 
board A1 
1. Output current must be greater than 2% of rated current to 
produce a High DC Voltage alarm. See 
Parallel Operation portion
in Section 2.3.6.
2. Turn off both front panel circuit breakers (or turn off ac and dc 
power externally if the charger doesn’t have breakers). Then turn 
on the dc breaker, followed by the ac breaker. If the charger 
output voltage is above the alarm setting, but the 
HIGH DC VOLTAGE indicator still doesn't light, replace the 
control circuit board. 
