APPENDIX A

70

SPECIFICATIONS

Except as noted, all specifications apply at:

77

°

° F / 25 °°C, nominal ac line voltage & nominal float voltage

Specification

Conditions

12 Vdc

24 Vdc

48 Vdc

130 Vdc

Output voltage regulation

Vac +10%, -12%
0 to 100% load
Temp. 32-122

°

F / 0-50

°

C

Freq. 60

±

3 Hz

±

0.25%

(see product literature for specific data)

Transient response

20-100% load change, with
battery connected

Output voltage change

±

4% maximum

Recovery to

±

2.0% in 200 ms

Recovery to

±

0.5% in 500 ms

30 Adc rating, full load, %

61

74

83

90

Efficiency

75 Adc rating, full load, %

62

75

84

91

1% rms (typ.)

2% rms

Unfiltered (with battery)

at battery terminals

30 mV rms (max.)

100 mV

Filtered (with battery)

at battery terminals

Filtered (without battery)

1% rms (typ.)

2% rms

Output ripple voltage
(per

NEMA PE5-1996)

Battery Eliminator Filter
Option (without battery)

30 mV rms

100 mV

Current limit

Adjustable

50-110 % of rated output current

Soft start

0 to 100% load

4 seconds

Float

11.0-14.5 22.0-29.5 44.0-58.0 110-141

Equalize

11.7-15.5 23.4-31.0 46.8-59.0 117-143

High DC Voltage alarm

12-19

24-38

48-76

120-175

Voltage adjustment ranges

Low DC Voltage alarm

7-14.5

15-29.5

30-58

80-141

Voltmeter range (Vdc)

0 - 21

0 - 42

0 - 75

0 - 195

Ammeter range (Adc)

All ratings

0 - 150

Surge withstand capability

Test per

ANSI C37.90.1-1989

No erroneous outputs

Reverse current from
battery

AC input power failure,
no options installed

90 mA maximum

Audible noise

Average for 4 sides
5ft / 1.5m from charger

Less than 62 dB(A)

Cooling

Natural convection

Ambient temperature

Operating

32-122

°

F / 0-50

°

C

Elevation

3000ft / 1000m without derating

Relative humidity

0 to 95% non-condensing

Alarm relay contact rating

120 Vac / 125 Vdc

0.5 A resistive