Operating the at10.1 – Exide Technologies Section 94.30 User Manual
Page 29
OPERATING THE AT10.1
25
•
If you have an optional temperature compensation probe installed, the
front panel displays
LEAD during startup, indicating that the
temperature compensation is set up for lead-acid batteries. While this is
being displayed, you can press any front panel key to change the display
to read
NICD, to change the temperature compensation setup for nickel
cadmium batteries. The choice you make is saved internally, and will be
used again by the AT10.1 then next time it starts.
•
Turn on the front panel ac circuit breaker. The digital meter displays the
output voltage and current. See
Using the Digital Meter on page 24. You
should hear a soft hum from the AT10.1 as the output current increases.
NOTE: If you turn on the ac breaker before the dc breaker,
and you have a filtered model of the AT10.1, there is a
possibility that the dc breaker will trip when you try to turn it
on. This is caused by the filter capacitors discharging into the
battery. To get around this problem, turn off the ac breaker.
Restart the AT10.1 by turning on the dc breaker first.
•
The green
FLOAT indicator lights. Press the
CHRG MODE
key on the
front panel. The
FLOAT indicator goes off, and the yellow EQLZ
indicator lights. Press the
CHRG MODE
key again to return the charger to
the float mode.
The table below shows the normal factory settings for float and equalize
voltage, equalize time, current limit setting, and alarm settings. If your
purchase order specified other float or equalize voltage settings, a tag
attached to the front panel of the AT10.1 lists the actual voltage settings.
FACTORY SETTINGS FOR ALL PARAMETERS
Nominal Vdc
Parameter
12
24
48
130
Float Voltage
13
26
52
131
Equalize Voltage
14
28
56
139
HVDC Alarm
14.4
28.8
57.6
144
LVDC Alarm
12
24
48
120
Equalize Time
24 Hours
Equalize Method
Manual Timer
Current Limit
110% of nominal output current
HVDC Shutdown
Disabled