Error messages – tekmar 362 Mixing Control Installation User Manual

Page 32

background image

32 of 36

Copyright © D 362 -

12/08

3 to 40 min, OFF

default = OFF

This item is an adjustable warning. If either the boiler or mixing
supply temperature does not begin to increase within the set
amount of time when required, the control will display a warning
message.

MODE = —1—

0 - 255

The number of times that the microprocessor in the control has
reset since this item was last cleared. The control will reset
itself if it has experienced some form of interference that has
disrupted its operation. This can be used to give an indication
of the quality of the electrical environment that the control has
been installed in.

0 - 255

The number of times that the control has been powered up
since this item was last cleared. This number will increase if
there is a lowering of the input voltage beyond the control’s
usable range. This item can be used as an indication of the
quality of the power source.

The number of times that a communication error has been
detected between the control and either an RTU, RDM or
Remote Start / Stop Module since this item was last cleared.
If the wires between the control and the tekmar Net

TM

(tN1/tN2)

device are run in a noisy electrical environment, this can cause
interference in the communication between the control and the
tN1/tN2 device.

0 - 255

362 Monitor Menu (3 of 3)

LT

D

INST ADV

Range

Access
Level

Description

Item Field

USER

Note: To clear the recorded Information in the specific item field, press and hold and .

362 Error Messages (1 of 4)

Error Displayed

Description of Error

The control was unable to store a piece of information into its EEPROM. This error can be caused by
a noisy power source. The control will display the error message and will continue to operate as normal.
Pressing either the Menu or Item button will clear this error.

The control was unable to read a piece of information stored in the Adjust menu. Because of this, the
control was required to load the factory settings into all of the items in the Adjust menu. The control
will stop operation until all of the items available in the Adjust menu of the control have been checked
by the user or installer.

Note: Access level must be ADV in order to clear the error.

The control was unable to read a piece of information stored in the Monitor menu. Because of this,
the control was required to load the factory settings into all of the items in the Monitor menu. The
control will continue to display the error message until all of the items available in the Monitor menu
of the control have been checked by the user or installer.

Note: Access level must be ADV in order to

clear the error.

The control was unable to read a piece of information stored in the Schedule menu. Because of this,
the control was required to load the factory settings into all of the items in the Schedule menu. The
control will continue to display the error message until all of the items available in the Schedule menu
of the control have been checked by the user or installer.

Note: Access level must be ADV in order to

clear the error.

The control was unable to read a piece of information stored in the Miscellaneous menu. Because of
this, the control was required to load the factory settings into all of the items in the Miscellaneous
menu. The control will continue to display the error message until all of the items available in the
Miscellaneous menu of the control have been checked by the user or installer.

Note: Access level must

be ADV in order to clear the error.

MODE = 1 & 2