Testing the Control

The Mixing Control 362 has a built in test routine which is used to test the main control
functions. The 362 continually monitors the sensors and displays an error message whenever
a fault is found. See the following pages for a list of the 362’s error messages and possible
causes. When the

test button is pressed, the test light is turned on. The individual outputs and

relays are tested in the following test sequence.

TEST SEQUENCE

Each step in the test sequence lasts 10 seconds.

During the test routine, the test sequence is paused by pressing the

Test button. While paused, the control displays the testing step as

well as the word PAUS. If the

Test button is not pressed again for 5 minutes while the test sequence is paused, the control exits the entire

test routine. If the test sequence is paused, the

Test button can be pressed again to advance to the next step. This can also be used

to rapidly advance through the test sequence. To reach the desired step, repeatedly press and release the

Test button until the

appropriate device and segment in the display turn on.

Step 1

- If FLOT is selected in the MIXING item, the mixing valve is run fully open. If VAR is selected in the MIXING item, the injection

pump is ramped up over 10 seconds to 100%.

Step 2

- If FLOT is selected in the MIXING item, the mixing valve is run fully closed. If VAR is selected in the MIXING item, the injection

pump is ramped down over 10 seconds.

Step 3

- The mixing pump

(Mix Pmp) is turned on for 10 seconds. NOTE: Only if there is a mixing demand can the control be paused

in step 3.

The type of setback override that is in effect.

DIP switch =

Setback

Away is available even if DIP

≠ Setback

NONE, TMPY Occ Ovr, PERM
Occ Ovr, TMPY UnOcc Ovr,
PERM UnOcc Ovr, AWAY Ovr

Default = NONE

362 RTU Schd (Schedule) Menu (1 of 1)

RTU

063

RTU

062

Section

LT

D

INST ADV

Range

Access
Level

Description

Item Field

USER

B1

362 RTU Misc (Miscellaneous) Menu (1 of 1)

RTU

063

RTU

062

The access level that is to be used by the RTU.

DIP switch =

Unlock

˚F, ˚C

Default =

°F

OFF, 30 sec, ON

Default = 30 sec

ADV, INST, USER, LTD

Default = INST

The units of measure that all of the temperatures are
to be displayed in the RTU.

The operating mode for the back lighting on the LCD
as well as the time of keypad inactivity until the RTU
automatically returns to the view menu.

BACKLITE = OFF (returns after 10 seconds)
BACKLITE = 30

sec (returns after 30 seconds)

BACKLITE = ON (returns after 90 seconds)

LT

D

INST ADV

Range

Access
Level

Description

Item Field

USER