Mixing valve actuator, Sensor and unpowered input connections, Outdoor sensor – tekmar 362 Mixing Control Installation User Manual

Page 17: Boiler sensor, Mixing sensor, Mixing return sensor, 10k sensor, Zone control input, Tekmar net, Device (tn1 / tn2)

background image

17 of 36

Copyright © D 362 -

12/08

8

9

Pwr

Mix

Opn Cls /

Var

10

24 or 120 V (ac)

Com

C

R

17

18

Com

Mix Boil

19

20

Out

17

18

Com

Mix

Boil

19

20

Out

Boiler
sensor

17

18

Com Mix

Mixing
sensor

14

15

Com 10K

14

15

10K

Com

Com
Sen

Zo

Out

tekmar 362

Zone Control

11

12

Com

Mix

Ret

tN1/

tN2

13

Item

Menu

UnOcc 1

°F

View

Heat

11

12

Com Mix

Ret

Mixing
Return
Sensor

Mixing Valve Actuator

Connect one side of the 24 V (ac) power to the

Pwr Mix terminal (8)

on the control. The output relay

Opn (9) is then connected to the

open terminal of the actuating motor and the output relay

Cls / Var

(10) is connected to the close terminal of the actuating motor.
Connect the second side of the 24 V (ac) circuit to the common
terminal of the actuating motor.

Sensor and Unpowered Input Connections

Do not apply power to these terminals as this will damage the
control.

Outdoor Sensor

Connect the two wires from the Outdoor Sensor 070 to the

Com and

Out terminals (17 and 20). The Outdoor Sensor is used by the 362
to measure the outdoor air temperature.

Boiler Sensor

Connect the two wires from the Boiler Sensor 071 to the

Com and

Boil terminals (17 and 19). The Boiler Sensor is used by the 362 to
measure the supply (outlet) water temperature from the boiler.

Mixing Sensor

Connect the two wires from the Mixing Sensor 071 to the

Com and

Mix terminals (17 and 18). The Mixing Sensor is used by the 362 to
measure the supply water temperature after the mixing device.
Normally the sensor is attached to the pipe downstream of the
mixing pump.

Mixing Return Sensor

Connect the two wires from the Mixing Return Sensor 071 to the
Com and Mix terminals (11 and 12). The Mixing Return Sensor is
used by the 362 to measure the fluid return temperature from the
snow melting slab.

10K Sensor

Either an Indoor Sensor, Slab Sensor, or Zone Control can be
connected to the

10K input. If a sensor is used, connect the two

wires from the sensor to the

Com and 10K terminals (14 and 15).

Zone Control Input

If an external tekmar Zone Control is used, connect the wire from the
Com Sen terminal on the Zone Control to the Com terminal (14) on
the 362. Connect the

Zo Out terminal on the Zone Control to the 10K

terminal (15) on the 362.

Note: The wires from the Zone Control are polarity sensitive. The
communication does not operate correctly if the wires are reversed.

tekmar Net

TM

Device (tN1 / tN2)

A Room Temperature Unit (RTU) 062 or 063, Remote Display
Module (RDM) 040, or a Remote Start / Stop Module 039 can be
connected to the tekmar Net

TM

(tN1 / tN2) input. Connect the Com

terminal from the appropriate device to the

Com terminal (11) on the

362. Connect the tN1 or tN2 terminal from the appropriate device to
the

tN1 / tN2 terminal (13) on the 362.

Note: The wires from the RTU, the RDM, and Remote Start / Stop
Module are polarity sensitive. The tN1/tN2 device does not operate
correctly if the wires are reversed.