beautypg.com

Schd (schedule) menu, Misc. menus – tekmar 362 Mixing Control Installation User Manual

Page 25

background image

25 of 36

Copyright © D 362 - 12/08

362 Adjust Menu (4 of 4)

Actual

Setting

The maximum length of time that the mixing pump

continues to operate after the mix demand

is removed.

OFF, 0:10 to 40:00 min

Default = 0:20 min

Enables or disables the Soft Start feature in

the control.
MODE = —1—

NONE, MIX

Default = NONE

The frequency with which the control exercises the

pumps and valves that are operated by the control.

30 to 240 hr, OFF

Default = 70 hr

Section

LT

D

INST ADV

Range

Access

Level

Description

Item Field

USER

B1

C1

B1

A

The type of setback override that is in effect for

the heating system.
DIP switch =

Setback

MODE = —1—
AWAY is available even if DIP ≠ Setback

NONE, TMPY Occ Ovr, PERM

Occ Ovr, TMPY UnOcc Ovr,

PERM UnOcc Ovr, AWAY Ovr

Default =NONE

The override that is in effect for the snow melting

system.
MODE = —2—

NONE, AWAY

Default =NONE

362 Schd (Schedule) Menu (1 of 1)

Section

LT

D

INST ADV

Range

Access

Level

Description

Item Field

USER

B1

C1

˚F, ˚C
Default = °F

The units of measure that all of the temperatures are to be

displayed in by the control.

362 Misc (Miscellaneous) Menu (1 of 2)

LT

D

INST ADV

Range

Access

Level

Description

Item Field

USER

362 Monitor Menu (see pages 30 - 32)