362 Monitor Menu (2 of 3)

The total number of hours the boiler has been firing since this
item was last cleared. The boiler running time may be longer
since this firing time does not include the FIRE DLY time set in
the Adjust menu. This item can be used to determine if the
boiler has been oversized or undersized for the attached heating
load. If the boiler does not run for a high percentage of time
when the outdoor temperature is near the design temperature,
the boiler has most likely been oversized. If the boiler runs
constantly but does not maintain the building temperature at
design conditions, the boiler has been undersized.

Boil SENS = SUP

0 to 9999 hr

The highest recorded temperature at the mixing sensor since
this item was last cleared.

-31 to 266˚F
(-35 to 129˚C)

The lowest recorded temperature at the mixing sensor since
this item was last cleared.

-31 to 266˚F
(-35 to 129˚C)

The total number of mixing pump

(Mix Pmp) running hours

since this item was last cleared.

0 to 9999 hr

The total number of firing cycles that the boiler has had since
this item was last cleared. This item can be used in conjunction
with the Boil FIRE item to determine the average cycle length
of the boiler. The cycle length of the boiler is related to the
differential that the boiler is operating with. If the cycle length
is too short, a larger differential may allow a longer cycle length.

Boil SENS = SUP

0 to 9999

The highest temperature recorded at the boiler sensor since
this item was last cleared.

Boil SENS

≠ NONE

The lowest temperature recorded at the boiler sensor since
this item was last cleared.

Boil SENS

≠ NONE

-31 to 266˚F
(-35 to 130˚C)

-31 to 266˚F
(-35 to 130˚C)

This item is an adjustable warning that can only be viewed if
the 10K item has been set to INDR. If the air temperature
measured by the indoor air sensor exceeds this setting, the
control will display a warning message.

10K = INDR

MODE = —1—

50 to 150˚F
(10 to 66˚C)

default = 110

°F (43°C)

0 to 80˚F
(-18 to 27˚C)

default = 45

°F (7°C)

This item is an adjustable warning that can only be viewed if
the 10K item has been set to INDR. If the air temperature
measured by the indoor air sensor drops below this setting,
the control will display a warning message.

10K = INDR

MODE = —1—

LT

D

INST ADV

Range

Access
Level

Description

Item Field

USER

Note: To clear the recorded Information in the specific item field, press and hold and .