362 Adjust Menu (2 of 4)

Actual

Setting

The

maximum length of morning boost.

DIP switch =

Characterized Heating Curve

DIP switch =

Setback

No RTU Connected
10K

≠ ZoIn

MODE = —1—

0:20 to 8:00 hrs

Default = OFF

0 to 50˚F
(0 to 28˚C)

Default = 15

°F (-9°C)

The minimum supply water temperature for the
mixing system.

DIP switch =

Characterized Heating Curve

MODE = —1—

OFF, 35 to 150˚F
(OFF, 2 to 66˚C)

Default = OFF

The design indoor air temperature used in the
heat loss calculations for the heating system.

DIP switch =

Characterized Heating Curve

MODE = —1—

35 to 100˚F
(2 to 38˚C)

Default = 70

°F (21°C)

The starting water temperature used in the Reset
Ratio calculation for the heating system.

DIP switch =

Reset Ratio

MODE = —1—

35 to 150˚F
(2 to 66˚C)

Default = 70

°F (21°C)

The outdoor starting temperature used in the
reset ratio calculation for the heating system.

DIP switch =

Reset Ratio

MODE = —1—

35 to 85˚F
(2 to 29˚C)

Default = 70

°F (21°C)

The amount the mixing supply temperature is
r e d u c e d w h e n t h e c o n t r o l i s i n t h e
UnOccupied Mode.

DIP switch =

Reset Ratio

DIP switch =

Setback

MODE = —1—

The design supply water temperature used in the
heat loss calculation for the heating system.

MODE = —1—

70 to 220˚F
(21 to 104˚C)

Default = 120

°F (49°C)

The type of terminal units that are being used in
the heating system.

DIP switch =

Characterized Heating Curve

MODE = —1—

HRF1 (Heavy), HRF2
(Light), (Fan-) COIL,
CONV (ector), RAD
(iator), BASE (board)

Default = HRF1

The design outdoor air temperature used in the
heat loss calculation for the heating system

MODE = —1—

-60 to 32˚F
(-51 to 0˚C)

Default = 10

°F (-12°C)

The maximum supply

temperature allowed

80 to 210˚F, OFF
(27 to 99˚C, OFF)

Default = 140

°F (60°C)

The type of mixing device that is to be used.

FLOT (Floating),
VAR (Variable speed)

Default = VAR

Section

LT

D

INST ADV

Range

Access
Level

Description

Item Field

USER

B1

B1

B1

B1

B1

B1

B1

B1

A

B1

A

B1

for the mixing system.