tekmar 362 Mixing Control Installation User Manual
Page 23
23 of 36
Copyright © D 362 -
12/08
362 Adjust Menu (2 of 4)
Actual
Setting
•
•
The
maximum length of morning boost.
DIP switch =
Characterized Heating Curve
DIP switch =
Setback
No RTU Connected
10K
≠ ZoIn
MODE = —1—
0:20 to 8:00 hrs
Default = OFF
0 to 50˚F
(0 to 28˚C)
Default = 15
°F (-9°C)
•
The minimum supply water temperature for the
mixing system.
DIP switch =
Characterized Heating Curve
MODE = —1—
OFF, 35 to 150˚F
(OFF, 2 to 66˚C)
Default = OFF
•
•
The design indoor air temperature used in the
heat loss calculations for the heating system.
DIP switch =
Characterized Heating Curve
MODE = —1—
35 to 100˚F
(2 to 38˚C)
Default = 70
°F (21°C)
•
•
The starting water temperature used in the Reset
Ratio calculation for the heating system.
DIP switch =
Reset Ratio
MODE = —1—
35 to 150˚F
(2 to 66˚C)
Default = 70
°F (21°C)
•
•
The outdoor starting temperature used in the
reset ratio calculation for the heating system.
DIP switch =
Reset Ratio
MODE = —1—
35 to 85˚F
(2 to 29˚C)
Default = 70
°F (21°C)
•
•
•
The amount the mixing supply temperature is
r e d u c e d w h e n t h e c o n t r o l i s i n t h e
UnOccupied Mode.
DIP switch =
Reset Ratio
DIP switch =
Setback
MODE = —1—
•
•
The design supply water temperature used in the
heat loss calculation for the heating system.
MODE = —1—
70 to 220˚F
(21 to 104˚C)
Default = 120
°F (49°C)
The type of terminal units that are being used in
the heating system.
DIP switch =
Characterized Heating Curve
MODE = —1—
•
•
HRF1 (Heavy), HRF2
(Light), (Fan-) COIL,
CONV (ector), RAD
(iator), BASE (board)
Default = HRF1
•
•
The design outdoor air temperature used in the
heat loss calculation for the heating system
MODE = —1—
-60 to 32˚F
(-51 to 0˚C)
Default = 10
°F (-12°C)
•
•
The maximum supply
temperature allowed
80 to 210˚F, OFF
(27 to 99˚C, OFF)
Default = 140
°F (60°C)
•
•
The type of mixing device that is to be used.
FLOT (Floating),
VAR (Variable speed)
Default = VAR
Section
LT
D
INST ADV
Range
Access
Level
Description
Item Field
USER
B1
B1
B1
B1
B1
B1
B1
B1
A
B1
A
B1
for the mixing system.