Rtus 062 and 063 – tekmar 362 Mixing Control Installation User Manual

Page 26

background image

26 of 36

Copyright © D 362 -

12/08

RTU View Menu

Item

Menu

UnOcc 1

°

F

View

Heat

The access level that is to be used by the control.

DIP switch =

Unlock

OFF, 30 sec, ON

Default = ON

ADV, INST, USER, LTD

Default = INST

The operating mode for the back lighting on the LCD as well
as the time of keypad inactivity until the control automatically
returns to the default display.

BACKLITE = OFF

(returns after 10 seconds)

BACKLITE = 30 sec (returns after 30 seconds)
BACKLITE = ON (returns after 90 seconds)

362 Misc (Miscellaneous) Menu (2 of 2)

LT

D

INST ADV

Range

Access
Level

Description

Item Field

USER

RTU

062

Current room air temperature.

RTU SENS = AIR

- - -, 14 to 167˚F
(-10 to 75˚C)

Target room air temperature.

RTU SENS = AIR

- - -, 35 to 100˚F
(2 to 38˚C)

Current outdoor air temperature.

-67 to 149˚F
(-55 to 65˚C)

Current slab (floor) sensor temperature.

REMOTE 3 = SLAB

-58 to 167˚F
(-50 to 75˚C)

RTU

063

• •

362 RTU View Menu (1 of 1)

Section

LT

D

INST ADV

Range

Access
Level

Description

Item Field

USER

B2

B2

B2

Room Temperature Units (RTUs) 062 and 063

A single RTU may be connected to the Mixing Control 362 in order to provide the control with indoor
temperature feedback for the mixing side of the heating system (Refer to Essay E 002). When using
an RTU, several items related to the mixing side of the heating system are no longer available in the
control’s User Interface. These items are available only in the RTU’s User Interface. Also, the number
of items that are available on the RTU depends on the type of RTU that is connected to the control.