Appendix – Banner A-GAGE MINI-ARRAY Series User Manual
Page 41

P/N 43298 rev. E
41
Banner Engineering Corp.
•
Minneapolis, MN U.S.A.
www.bannerengineering.com • Tel: 763.544.3164
MINI-ARRAY
®
Instruction Manual
Appendix
Figure A-2. Serial Communication Options
Figure A-2 shows that the binary transmission has three independent options.
These options are independently selected and are used to custom-configure the
serial data format. The
Suppress Clear Data
option is applicable when the sensor
is unobstructed. While the sensor is blocked, serial data is transmitted; once the
sensor is unobstructed, the “clear” data is transmitted once, and then no further data
transmission occurs until the sensor is again blocked. The
Suppress Header
option
will serially transmit the array data bytes. The three header bytes are not transmitted.
The
Compress Data
option affects the data bytes for the measurement modes
excluding the
ALL
mode. Except for the
ALL
mode, the analysis modes use two bytes
to transmit the appropriate information. For cases where the sensor cannot provide a
result greater than 255, the
Compress Data
option will provide this data in one byte.
As an example, assume that you have a 48-channel sensor with a last beam blocked
of 35 and a controller ID of “B.” Assume two binary format options. The first option is
the standard
Binary Transmission
format. The second format will use the
Suppress
Header
and
Compress Data
options. The two strings would be as follows:
Option 1:
Binary Transmission
0x1c B 0x00 0x23 0x0a (a total of 5 bytes per scan)
Option 2:
Binary Transmission, Suppress Header, Compress Data
0x23 (1 byte per scan)