beautypg.com

18 ▪▪▪▪▪▪▪ sequence 4: safe pressure achieved – Metrohm NIRS XDS Process Analyzer – SingleFiber User Manual

Page 20

background image

18

▪▪▪▪▪▪▪

Sequence 4:

Safe Pressure Achieved

ENCLOSURE

POWER

DISENGAGED

SAFE

ENCLOSURE

PRESSURE

RAPID

EXCHANGE

FLOW

RAPID

EXCHANGE

TIMER

HIGH

ENCLOSURE

PRESSURE

ENCLOSURE

POWER

ENGAGED

PRESSURE

LOSS

ALARM

SYSTEM

CONTROL

BYPASSED

POWER

SHUTDOWN

DELAY

EMERGENCY

POWER

SHUTDOWN

RAPID

EXCHANGE

OVERRIDE

EPCU

POWER

ENGAGED

HEP

SEP

SDT

RET

SERIES 4000 ELECTRONIC POWER CONTROL UNIT

Apply air to achieve Safe Pressure

When Safe Pressure Setpoint is achieved,
Safe Enclosure Pressure LED is ON.

Factory setting for Safe Pressure
Setpoint = 1.5” water.

Sequence 5:

Rapid Exchange Solenoid Energized

ENCLOSURE

POWER

DISENGAGED

SAFE

ENCLOSURE

PRESSURE

RAPID

EXCHANGE

FLOW

RAPID

EXCHANGE

TIMER

HIGH

ENCLOSURE

PRESSURE

ENCLOSURE

POWER

ENGAGED

PRESSURE

LOSS

ALARM

SYSTEM

CONTROL

BYPASSED

POWER

SHUTDOWN

DELAY

EMERGENCY

POWER

SHUTDOWN

RAPID

EXCHANGE

OVERRIDE

EPCU

POWER

ENGAGED

HEP

SEP

SDT

RET

SERIES 4000 ELECTRONIC POWER CONTROL UNIT

Rapid Exchange Solenoid
engaged after 3 second delay

The following conditions must be satisfied:

Flow Switch

High Pressure Channel

Factory Setting = 8 in. water

Low Pressure Channel

Sequence 6:

Rapid Exchange Timer cycle begins

Sequence 7:

Rapid Exchange Timer cycle complete

ENCLOSURE

POWER

DISENGAGED

SAFE

ENCLOSURE

PRESSURE

RAPID

EXCHANGE

FLOW

RAPID

EXCHANGE

TIMER

HIGH

ENCLOSURE

PRESSURE

ENCLOSURE

POWER

ENGAGED

PRESSURE

LOSS

ALARM

SYSTEM

CONTROL

BYPASSED

POWER

SHUTDOWN

DELAY

EMERGENCY

POWER

SHUTDOWN

RAPID

EXCHANGE

OVERRIDE

EPCU

POWER

ENGAGED

HEP

SEP

SDT

RET

SERIES 4000 ELECTRONIC POWER CONTROL UNIT

Rapid Exchange ends

Solenoid De-engaged

Enclosure Power energized