beautypg.com

Define alarm conditions – Rockwell Automation FactoryTalk Alarms and Events Quick Start User Manual

Page 73

background image

6

Add a tag-based alarm server for Logix5000, PLC-5, SLC 500, or third-party controllers

• •
• •

65

Define alarm conditions

After you create a Tag Alarm and Event Server, you define the conditions that will
trigger alarms at run time.

This example shows how to create a digital alarm in a Tag Alarm and Event Server.

1. In the Explorer window, expand the TagAE server, and then double-click Alarm

and Event Setup.

2. In the Alarm and Event Setup dialog box, click the New button on the toolbar,

and then click Digital.

3. In the Digital Alarm Properties dialog box, type a name for the alarm. In this

example we used Valve1FTO.

4. To select an Input Tag for the alarm, click the browse button, and then expand the

folder folder tree until you can select the online tag you plan to monitor.