beautypg.com

Rockwell Automation 2727-G7P20D1Q7 MobileView Guard G750 Quick Start User Manual

Page 16

background image

16 MobileView Guard G750

Publication 2727-QS002E-MU-P

Power Supply Requirements

Electrical Specifications

24V dc Power Supply

Use a 24V dc Safety Extra Low Voltage power supply.
Supply Voltage Range: 18V dc to 32V dc
Current Consumption: 300mA at 24V dc
Peak Inrush Current: 5.6 A maximum

Grounding

Connect Earth Ground to the Junction Box using the Earth
Ground Screw (shown on page 14).

ATTENTION

!

• The device meets the safety class III in accordance with EN

61131-2 and EN 50178. The 24V power supply for the
equipment must provide appropriate isolation between the
safety-extra-low-voltage circuits and dangerous-contact
voltage circuits (for example, by safety transformers or
similar facilities).

• The power supply circuit must be protected with a 3.15 A

fuse.

• The nominal supply voltage directly of the MobileView

terminal (without the MobileView Connection Cable) is
+24V dc (supply voltage range: 18 to 32V dc).

Typical current consumption is:
- 300 mA at 24V dc
-400 mA at 18V dc
When planning the power supply, take into account the
voltage drop on the Connection Cable.
Specification of power supply lines in this cable:

Cross section: AWG24 (0.24 mm

2

)

Material: zinc-coated copper strand
Line resistance:

<

90 Ohm/km (

<

145

Ohm/mile)