Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive (A Frame) - ForGe Control User Manual
Page 200

200
Rockwell Automation Publication 7000A-UM200C-EN-P - June 2014
Appendix H
Specifications
Enclosure
NEMA 1 (standard)
IP21 (IEC)
IP42 (IEC) (optional)
Lifting Device
Standard / Removable
Mounting Arrangement
Mounting Sill Channels
Structure Finish
Epoxy Powder – Paint
Exterior Sandtex Light Grey (RAL 7038) – Black (RAL 8022)
Internal – Control Sub Plates – High Gloss White (RAL 9003)
Interlocking
Key provision for customer input Disconnecting Device
Corrosion Protection
Unpainted Parts (Zinc Plated / Bronze Chromate)
Ambient Temperature
0…40 °C (32…104 °F) / 0…50 °C (32…122 °F) - optional
Fiber Optic Interface
Rectifier – Inverter – Cabinet (Warning / Trip)
Door Filter
Painted Diffuser with Matted Filter or Washable Foam Media
Door Filter Blockage
Air Flow Restriction Trip / Warning
Storage and Transportation
Temperature Range
-40…70 °C (-40…185 °F)
Relative Humidity
Max. 95%, non-condensing
Altitude (Standard)
2400...4160V: 1001...5000m (3301...16,400 ft)
6000V: 1001...2000m (3301...6600 Ft)
Altitude (Optional)
1001…5000 m (0…16,400 ft)
Seismic (UBC Rating)
1, 2, 3, 4
Standards
NEMA, IEC, CSA, UL, ANSI, IEEE
(1) Voltage Sag tolerance is reduced to -25% when control power is supplied from medium voltage via CPT.
(2) Surge arrestors are used for AFE/Direct-to-Drive configurations.
(3) Short-circuit fault rating based on input protection device (contactor or circuit breaker).
(4) BIL rating based on altitudes < 1000 m (3300 ft). Refer to factory for derating on altitudes >1000 m.
(5) Optional.
(6) Under certain conditions, power system analysis will be required.
Table 13 - General Design Specifications
Description