Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive (A Frame) - ForGe Control User Manual
Page 140
![background image](/manuals/580543/140/background.png)
140
Rockwell Automation Publication 7000A-UM200C-EN-P - June 2014
Chapter 3
Component Definition and Maintenance
ACB-TP43
Vspr
Spare channel for inputs
ACB-TP44
Vmtrp
Motor Over Voltage Detection set point
ACB-TP45
A+
Encoder A+ input
ACB-TP46
B+
Encoder B+ input
ACB-TP47
Z+
Encoder Z+ input
ACB-TP48
A-
Encoder A-input
ACB-TP49
B-
Encoder B- input
ACB-TP50
Z-
Encoder Z- input
ACB-TP51
CP1
Control Power monitoring for channel 1
ACB-TP52
CP2
Control Power monitoring for channel 2
ACB-TP53
CP3
Control Power monitoring for channel 3
ACB-TP54
CP4
Control Power monitoring for channel 4
ACB-TP55
Vltrp
AC Over Voltage Detection set point for 2UVW&3UVW
ACB-TP56
AGND
Analog ground
ACB-TP57
AGND
Analog ground
ACB-TP58
AGND
Analog ground
ACB-TP59
AGND
Analog ground
ACB-TP60
+5V
+5V DC power supply
ACB-TP61
+15V
+15V DC power supply
ACB-TP62
-15V
-15V DC power supply
ACB-TP63
+24V
+24V DC power supply
ACB-TP64
-24V
-24V DC power supply
ACB-TP65
24VCOM
+/- 24V common
ACB-TP66
DGND
Digital ground
ACB-TP67
AGND
Analog ground
ACB-TP68
AP1
Analog Control Inputs, Air pressure input, AP1
ACB-TP69
AP0
Analog Control Inputs, Air pressure input, AP0
ACB-TP70
AIN1
Analog Control Input, AIN1
ACB-TP71
AIN2
Analog Control Input, AIN2
ACB-TP72
AIN0
Analog Control Input, AIN0
ACB-TP73
AIN3
Analog Control Input, AIN3
ACB-TP74
IPIS
Input Isolating Switch
ACB-TP75
IPCS
Input Contactor Status
ACB-TP76
IP
Input Contactor Command
ACB-TP77
OPIS
Output Isolating Switch
ACB-TP78
OPCS
Output Contactor Status
ACB-TP79
OP
Output Contactor Command
ACB-TP80
BPIS
Bypass Isolating Switch
ACB-TP81
BPCS
Bypass Contactor Status
ACB-TP82
BP
Bypass Contactor Command
ACB-TP83
DGND
Digital Ground Return