Rockwell Automation Publication 7000A-UM200C-EN-P - June 2014

141

Component Definition and Maintenance

Chapter 3

Interface Module (IFM)

The Interface Module is used to make all customer useable connections to the
ACB. The pin numbers listed on the following pages refer to IFM pin numbers.

Figure 113 - Interface Module

Analog Inputs and Outputs

The PowerFlex 7000 offers one isolated process current loop transmitter and
three isolated process current loop receivers, embedded into the control. These
are accessible on the ACB.

The isolated Process Output is configured as 4...20 mA. The three isolated
process inputs are individually configurable for either a range of -10/0/+10V or
4...20 mA (Refer to Programming Manual).

The following information shows the connections for each input and output.

Even pin numbers

Odd pin numbers

Connection to ACB (J8)