66
Rockwell Automation Publication 2080-UM004B-EN-E - December 2013
Appendix A Specifications
CJC error
—
±1.2 °C @ 25 °C (77 °F)
Accuracy
±1.0 °C for TC and RTD @ 25 °C (77 °F)
Channels
2, non-isolated
RTD types supported
100
Ω Platinum 385
200
Ω Platinum 385
500
Ω Platinum 385
1000 Platinum 385
100
Ω Platinum 392
200
Ω Platinum 392,
500
Ω Platinum 392
1000
Ω Platinum 392
10
Ω Copper 427
120
Ω Nickel 672
604
Ω Nickel-Iron 518
—
Thermocouple types supported
—
J, K, N, T, E, R, S, B
Open circuit detection time
8…1212 ms
8…1515 ms
Power consumption
3.3 V, 40 mA
Temperature, surrounding air, max.
65 °C (149 °F)
Temperature, operating
IEC60068-2-1 (Test Ad, Operating Cold),
IEC60068-2-2, (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...65 °C (-4…149 °F)
Temperature, nonoperating
IEC60068-2-1 (Test Ad, Operating Cold),
IEC60068-2-2, (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-40...85 °C (-40…185 °F)
North American temp code
T4
Certifications – 2080-TC2, 2080-RTD2
Certification (when
product is marked)
(1)
(1) See the Product Certification link at
for
Declarations of Conformity, Certificates, and other certification details.
Value
c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada.
See UL File E322657.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,
certified for U.S. and Canada. See UL File E334470.
CE
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
General and Environmental Specifications – 2080-TC2, 2080-RTD2
Attribute
2080-RTD2