Analog plug-in modules – Rockwell Automation 2080 Micro800 Digital and Analog Plug-in Modules User Manual
Page 70

62
Rockwell Automation Publication 2080-UM004B-EN-E - December 2013
Appendix A Specifications
Analog Plug-in Modules
Input Specifications – 2080-IF2, 2080-IF4
Attribute
2080-IF2
2080-IF4
Number of inputs, single ended
2
4
Analog normal operating ranges
Voltage: 0…10V DC
Current: 0…20 mA
Resolution, max.
12 bits unipolar, with software selected option for 50 Hz,
60 Hz,
250 Hz, 500 Hz
Data range
0…65535
Input impedance
Voltage Terminal: > 220K
Ω, Current Terminal: 250 Ω
Overall accuracy
(1)
(1) Includes offset, gain, non-linearity and repeatability error terms.
Voltage Terminal: ±1% full scale @ 25°C
Current Terminal: ±1% full scale @ 25°C
Non-linearity (in percent full scale)
± 0.1%
Repeatability
(2)
(2) Repeatability is the ability of the input module to register the same reading in successive measurements for the
same input signal.
± 0.1%
Module error over full temperature
range, -20…65°C (-4…149°F)
Voltage: ± 1.5%
Current: ± 2.0%
Input channel configuration
Through configuration software or the user program
Field input calibration
Not required
Update time
180 ms per enabled channel
Input group to bus isolation
No isolation
Channel to channel isloation
Non-isolation
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...65 °C (-4…149 °F)
Temperature, non-operating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock):
-40...85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5%...95% non-condensing
Operating altitude
2000 m
Cable length, max.
10 m
Output Specifications – 2080-OF2
Attribute
2080-OF2
Number of outputs, single ended
2
Analog normal operating ranges
Voltage: 10V DC
Current: 0…20 mA
Resolution, max.
12 bits unipolar
Output count range
0…65535
D/A Conversion Rate (all channels), max.
2.5 ms