beautypg.com

User defined function blocks, Ra_hscplugin – Rockwell Automation 2080 Micro800 Digital and Analog Plug-in Modules User Manual

Page 43

background image

Rockwell Automation Publication 2080-UM004B-EN-E - December 2013

35

High Speed Counter – 2080-MOT-HSC Appendix 4

User Defined Function
Blocks

RA_HSCPlugIn

The purpose of this UDFB is to get high speed counter accumulator value and
current pulse frequency.

1001

1000

999 Hz

1000 Hz

0.10%

9,999

10,000

100.01 Hz

100.00 Hz

0.010%

99,999

100,000

10.00010 Hz

10.00000 Hz

0.001%

(1) This table does not represent accuracy per pulse but repeatability. This repeatability can be applied in No

Filter setting.

Maximum Cyclic Rate Errors

Update Time
Value Scalar

Frequency

100 Hz

1 kHz

10 kHz

100 kHz

1 MHz

1

NA

NA

20.02%

20.02%

0.210%

10

NA

20.11%

2.020%

0.210%

0.030%

100

20.01%

2.110%

0.220%

0.031%

0.012%

1000

3.010%

0.310%

0.040%

0.013%

0.010%

10,000

1.210%

0.130%

0.022%

0.011%

0.010%

IMPORTANT

For low frequency pulses, filter times should be set appropriately to
avoid extra pulses from a noisy environment. For high frequency pulses,
shielded cable must always be used.

Per Pulse Errors

(1)

Real pulses
(note 1.9999 can
be rounded to 2)

Pulses
reported by
module

Real
Frequency

Reported
Frequency

% Error

RA_HSCPlugIn

FBEN

SlotID

NoiseFilter
Mode

FBENO

IDCheck

Start

Stop

Initialized

Accumulator

Rate