Rockwell Automation 2080 Micro800 Digital and Analog Plug-in Modules User Manual
Page 66
58
Rockwell Automation Publication 2080-UM004B-EN-E - December 2013
Appendix A Specifications
AC on-state current, min
2.0 mA @ 9V AC (rms)
AC on-state current, max
5.0 mA
AC off-state voltage
3.5V AC (rms)
Output Specifications – 2080-OB4, 2080-OV4, 2080-IQ4OB4, 2080-IQ4OV4
Attribute
Value
Power supply voltage
10.8V DC, min
30V DC, max
On-state voltage
10V DC, min
24V DC, nom
30V DC, max
On-state current
5.0 mA @ 10V DC, min
0.5 A max, steady state
2 A surge, 2 s min
Environmental Specifications – 2080-OB4, 2080-OV4, 2080-IQ4OB4,
2080-IQ4OV4, 2080-IQ4
Attribute
Value
Temperature, operating
IEC60068-2-1 (Test Ad, Operating Cold),
IEC60068-2-2, (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...65 °C (-4…149 °F)
Temperature, surrounding
air, max.
65 °C (149 °F)
Temperature, non-operating
IEC60068-2-1 (Test Ad, Operating Cold),
IEC60068-2-2, (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-40...85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
DIN rail mounting: 25 g
Panel mounting: 35 g
Shock, non-operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g
Emissions
CISPR 11:
Group 1, Class A
ESD Immunity
IEC 61000-4-2:
4 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
10 V/M with 1 kHz sine-wave 80%AM from 80…2000 MHz
10 V/M with 200 Hz 50% Pulse 100%AM @ 900 MHz
10 V/M with 200 Hz 50% Pulse 100%AM @1890 MHz
10 V/M with 1 kHz sine-wave 80%AM from 2000…2700 MHz
Input Specifications – 2080-IQ4, 2080-IQ4OV4, 2080-IQ4OB4
Attribute
Value