1785-6.5.19 November 1998

B-2

Performance Data

Workstation-to-PLC (Solicited Synchronous)

Operation:

Words:

MSG per second:

ms per MSG:

Words per second:

read

1

45.8

21.8

45

read

20

43.6

22.9

872

read

100

41.8

23.9

4,180

read

1000

23.3

42.9

23,300

write

1

45.4

22.0

45

write

20

44.3

22.6

886

write

100

41.7

24.0

4,170

write

1000

21.9

45.7

21,900