Installing the Interface Module

2-5

Installing the Interface Module

To install the PLC-5 Ethernet Interface Module, you must:

attach the connector header to the processor

attach adhesive washers to the processor

connect the interface module to the processor

install the combination into the chassis

Attach the Connector Header to the Processor

If you have not already done so, attach a grounding wrist strap to your
wrist. Then follow these steps to attach the connector header to the
processor:

!

ATTENTION: If your power supply is already
installed in the chassis, be sure the chassis power supply
is turned OFF before you begin the installation
procedures. Do not attempt to install the interface
module with chassis power ON. Installing the module
with chassis power ON will damage the module.

Attach the interface module to
this end of the connector header.

Locate the PLC-5 processor
connector header port.

Push the exposed pins into the
holes on the PLC-5 processor.